53
9. Additional functions and function setting changes for the UPS
4. Output voltage selection/Input power supply sensitivity selection settings
(Factory settings)
100V output/normal voltage sensitivity
Settings can be made by selecting from the following four modes:
●
100V AC output/normal voltage sensitivity
With input of 100V AC, output is 100V AC.
Power failure detection voltage is at normal setting.
•
At this setting, output voltage (output voltage varies depending on input voltage) ranges from around
90V AC to 110V AC.
•
The maximum output capacity at this setting is:
1000VA/700W (BN100XR)
1500VA/1000W (BN150XR)
2400VA/2000W (BN240XR)
●
100V AC output/low voltage sensitivity
With input of 100V AC, output is 100V AC.
Power failure detection voltage is 5V lower than normal setting.
•
At this setting, output voltage (output voltage varies depending on input voltage) ranges from around
90V AC to 110V AC.
•
The maximum output capacity at this setting is:
1000VA/700W (BN100XR)
1450VA/1000W (BN150XR)
2250VA/2000W (BN240XR)
●
115V AC output/normal voltage sensitivity
With input of 100V AC, output is 115V AC.
Power failure detection voltage is at normal setting.
•
At this setting, output voltage (output voltage varies depending on input voltage) ranges from around
100V AC to 125V AC.
•
The maximum output capacity at this setting is:
1000VA/700W (BN100XR)
1500VA/1000W (BN150XR)
2450VA/2000W (BN240XR)
●
115V AC output/low voltage sensitivity
With input of 100V AC, output is 115V AC.
Power failure detection voltage is 4V lower than normal setting.
•
At this setting, output voltage (output voltage varies depending on input voltage) ranges from around
95V AC to 125V AC.
•
The maximum output capacity at this setting is:
1000VA/700W (BN100XR)
1500VA/1000W (BN150XR)
2350VA/2000W (BN240XR)
5. Output receptacle delay time at UPS startup
(Factory setting)
Output receptacle B has no delay. Output receptacle C has no delay.
The output start time for output receptacles B and C at UPS startup can be set independently, and delayed
with respect to output receptacle A.
●
Output delay time setting
Values ranging from 0 (minimum value) to 10 minutes (maximum value) can be set.
6. Battery start date (replacement date) registration
(Factory setting)
No data.
It is possible to register and/or update the battery start/replacement date.
Register the battery start date for the purpose of battery replacement maintenance.