4) In the "UPS signal polarity" box, click on the boxes to the right of "Power supply failure/battery
drive (P)" and "Low battery (L)" signals to insert check marks.
Set the polarity for each signal to "Negative". Click the "End" button.
Click
Check
Check
Click
Click
5) Click the "OK" button in the "Power supply options" window.
Setup is complete.
When a power failure occurs, Windows shutdown starts once the Low battery level signal is de-
tected.
If the power is restored before the Low battery level signal is detected, Windows shutdown does
not start and the normal monitoring state is restored.
In the Windows Server 2003/XP/2000 UPS service, there is no function to stop the UPS. After Windows is
shut down, manually turn OFF the unit’s power switch.
Stopping the UPS