18
2. Installation and connection
2-5 Adding a battery unit (BU100XR2, BU200XR2)
2-6 Adding the UPS output receptacle (BU200XR2)
When two UPS output receptacles are not enough
and an additional receptacle is needed, simply
connect a supplied 15A output receptacle to the
"power supply output receptacle of the main unit."
Secure the 15A output receptacle on the rear side of
the battery unit with screws (M4 X 6mm, inch-thread
screws)
●
BU200XR2
Connect a "Battery Connecting Cable" included with
the battery unit between the "Batter y Add-on
Connector" of BU200XR2 and the "Battery Connector"
of an add-on battery unit. After putting an "AC Input"
plug in, a "Connection" lamp on the front panel of the
battery unit will light up. BU100XR2 permits up to two
ad-on battery units.
●
BU100XR2
Connect a "Battery Connecting Cable" included
with the battery unit between the "Battery Add-
on Connector" of BU100XR2 and the "Battery
Connector" of the battery unit. After putting an
"AC Input" plug in, a "Connection" lamp on the
front panel of the battery unit will light up.
BU100XR2 permits only one ad-on battery unit.
* For further information, see the instruction
manual of Battery Unit.
* For further information, see the instruction manual of
Battery Unit.
BU200XR2
MB200XR2
BU100XR2
Add-on
battery unit
MB100XR2
Add-on
battery unit
MB200XR2
Add-on
battery unit
MB200XR2
A backup time is 20 minutes in a case where
a 1KVA/700W device is connected. (ambient
temperature: 20
°
C, battery initial value) A
discharged battery requires twenty-four
hours to recharge fully.
The backup time is 10 minutes in a case where a
2KVA/1.4KW device is connected with one add-on
battery, and 20 minutes with two add-on batteries.
(ambient temperature: 20
°
C, battery initial value) A
discharged battery requires twelve hours to
recharge fully in the case of one add-on battery,
while it requires twenty-four hours in the case of
two add-on batteries.