19
2. Installation and connection
(5) Connect the AC Input Plug to a wall outlet (commercial
power) again.
The Battery mode Lamp goes out, the AC Input Lamp
goes on, and a beep stops.
(The status is as shown in the right figure.)
Checking the operation is now complete.
2-5 Charging the battery
When you connect the AC Input Plug of the UPS to a wall outlet (commercial power), charging the battery is
automatically started and it is fully charged for 8 hours or less.
(The UPS performs charging regardless of in operation or in pause.)
●
The UPS has been charged prior to shipment. However, the backup time becomes shorter when using it for
the first time due to spontaneous discharge.
We recommend charging the UPS before using it.
2-6 Measuring the backup time
When "2-4 Checking the operation" is complete, you can start actual operation. However, in order to know the
backup time in your use environment and use it as a guide for inspecting the battery, measure the initial value
of the backup time.
See also "5-1 Measuring method of the backup time" on page 28.
Goes
on
Goes
out
Goes on, blinks,
or goes out
depending
on the status.
100%
75%