(3) When you perform auto shutdown processing using the UPS management software of Windows XP/2000,
set the delay time.
See also
When performing the auto shutdown processing by Windows XP/2000's UPS management
software
➛
Page 38
●
Beeper ON/OFF setting (setting switch 3 ) … Factory-shipped setting: ON
ON:
The beeper sounds when an alarm is necessary.
OFF: The beeper does not sound when the Battery Mode starts. When the Alarm Lamp (red) goes on
or blinks (excess of connection capacity, battery replacement, abnormal operation, and so on),
the beeper sounds.
●
UPS Stop Signal setting (setting switch 4 ) … Factory-shipped setting: ON
ON:
You can stop power output from the UPS by inputting the UPS Stop Signal (HIGH) that lasts at
least 0.01 second (10 ms). The Stop Signal is accepted only in the Battery Mode to stop power
output.
After the output is stopped, when abnormal power such as a power failure is resolved, the UPS
automatically restarts.
If you do not want to stop the UPS in Commercial Power Mode even if the UPS Stop Signal is
inputted, use this setting.
OFF: You can stop power output from the UPS by inputting the UPS Stop Signal (HIGH) that lasts at
least 10 seconds. Voltage signal input stops power output even in Commercial Power Mode.
After the output is stopped, if commercial power is normal, the UPS automatically restarts.
●
Auto battery test ON/OFF setting (setting switch 5 ) … Factory-shipped setting: ON
ON: The battery test is automatically executed at intervals of 4 weeks.
OFF: The auto battery test is disabled.
If you want to disable Battery Mode for the test performed regularly, use this setting.
Setting switch 1 Setting switch 2
Power output stop delay time
OFF
OFF
Does not stop power output.
ON
OFF
0 second
OFF
ON
60 seconds
ON
ON
120 seconds
ON
1 2
3 4
5
ON
1 2
5
3 4
ON
1 2
5
3 4
ON
1 2
5
3 4