4
Safety precautions
Connect the unit to a wall outlet (commercial power) with a current capacity
larger than 12A.
●
Otherwise, the power cord may be heated.
●
When an equipment of the maximum output capacity is connected, the current flows up to
12A.
Provide secure grounding.
●
For a 3P wall outlet, directly connect the 100-VAC input plug of the unit to it. Not doing so may
cause an electric shock in the case of unit failure or electric leakage.
●
When you use a 3P-2P conversion plug for 100-VAC input plug, be sure to perform grounding
before connecting the 100-VAC input plug into a wall outlet (commercial power).
Do not disconnect the grounding before disconnecting the 100-VAC input plug from a wall
outlet (commercial power).
●
Grounding is necessary to enable its surge protection function.
Do not disassemble, repair, or modify the unit.
●
Doing so may cause an electric shock or a fire.
Do not install the unit in other than specified orientations.
●
Dropping or toppling the unit may cause injury.
●
If you install the unit in an orientation other than specified, the unit cannot be protected from a
battery fluid leakage.
When installing the unit vertically, do not put any object on it.
When installing the unit horizontally, do not put any object heavier than
25kg.
●
Doing so may cause distortion of/damage to the case, which may cause a fire.
Do not use the unit where the maximum temperature exceeds 40
°
C.
●
The battery becomes weak rapidly and may cause a fire.
●
Doing so may cause a failure or malfunction of the unit.
Do not install or store the unit in the places listed below.
●
The humidity is lower than 10%. The humidity is higher than 85%. A closed place such as in a
cabinet without clearance. There is flammable gas or corrosive gas. A place subject to vibra-
tion or shock. Outdoors.
●
Installation or storing the unit in such a place may cause a fire.
Do not use the unit in a closed place or do not cover the unit.
●
Doing so may cause abnormal heating or a fire.
Do not connect equipment that exceeds the output capacity of the unit.
●
The current protection of the unit may operate, which may stop the output.
●
The wiring of the plug strip heats up, which may cause a fire.
Do not pinch or tie the cable of the unit.
●
Doing so may cause the cable to be damaged or heated, which may cause an electric shock
or a fire.
●
If the cable is damaged, stop using the unit and the cable must be repaired.
For repair, contact us; ____
Caution
(for installation and connection)
05-safty-p3-8
03.6.20, 11:11 AM
Page 4
Adobe PageMaker 6.5J/PPC