5
Safety precautions
Do not wet or pour water onto the unit.
●
Doing so may cause an electric shock or a fire.
●
If you wet the unit, stop using it and the unit must be inspected and/or repaired.
For repair, contact us; ____
When the battery is dead, replace it immediately or stop using the unit.
●
Continuing the use of it may cause a fire.
Wipe the 100-VAC input plug clean of dirt with a dry cloth occasionally.
●
Settled dust may cause a fire.
If you notice abnormal sound or smell, smoke, or leakage from the inside,
immediately turn off the power switch and disconnect the 100-VAC input
plug from a wall outlet (commercial power).
●
Using the unit under such conditions may cause a fire.
●
If you notice such a condition, never use the unit and contact us; ____ for inspection and
repair.
●
Use the unit under the conditions in which you can immediately disconnect the 100-VAC input
plug from a wall outlet (commercial power) in the case of an abnormal event.
If fluid leaks from the unit, do not touch the fluid.
●
Doing so may cause blindness or burns.
●
If the fluid contacts your eyes or skin, wash it out with lots of clean water and consult your
doctor.
Caution
(for use)
* The values in the table are the expected life under standard
use conditions and are not guaranteed.
Ambient temperature
20
°
C
30
°
C
Expected life
4 to 5 years
2 to 2.5 years
Caution
(for installation and connection)
●
This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit The
unit contains no user serviceable parts.Only factory service personnel may perform repairs.
●
Connection to any other type of receptacle other than a two-pole,three-wire grounded recep-
tacle may result in shock hazard as well as violate local electical codes.
●
Do not allow liquids or any foreign object to enter the UPS.DO not place beverages or any
other liquid-containing vessels on or near the unit.
●
This unit intended for installation in a controlled environment (temperature controlled, indoor
area free of conductive contaminants).Avoid installing the UPS in locations where there is
standing or running water,or excessive humidity.
●
Do not attach a power strip or surge suppressor to the UPS.
●
Do not attach non-computer-related items,such as medical equipment,life-support
equipment,microwave ovens,or vacuum cleaners to UPS
●
With the installation of the equipment it should be prevented, that the sum of the leakage
current of the UPS and the connected consumer does not exceed 3.5mA.