When you connect the AC input plug of this unit to a wall outlet (commercial power), the bat-
tery charging automatically starts regardless of whether the power switch is ON or OFF, and it 
is fully charged within 12 hours.

(Charging is performed regardless of whether the power switch is ON or OFF.)

  This unit has been charged prior to shipment. However, the backup time becomes shorter when 

using it for the fi rst time due to spontaneous discharge. We recommend charging this unit before 
using it.

  If you do not perform the initial backup time measurement described below in “2-6 Measuring the 

initial value of backup time”, proceed to “3. Operation. 

 Page 15”

2-5 

Charging the battery

2-7 

Recharging the battery

2-6 

Measuring the initial value of backup time

 

When you measure the backup time initial value of the unit in your environment, this value can 
be used as a guide when checking the battery and deciding the UPS monitoring software set-
ting values. 

 

See also

  "5. Measuring the backup time" 

 Page 28

The battery is discharged completely when the backup time is measured, so you need to recharge it 
before using the UPS.

  You can use connected devices while recharging the battery, but the backup time when a power 

failure occurs is shorter until the battery is fully charged.

 

(If a power failure occurs immediately after the start of charging, backup stops immediately.)

  

See also

  Charge the battery as described in "2-5 Charging the battery." 

Preparation for starting operation is now complete.

2

.Installation and connection

14

Summary of Contents for Powli BY120S

Page 1: ...stand this manual before installing and using the product Keep this manual in a convenient location so that you can refer to it whenever necessary The contents of this manual are subject to change wit...

Page 2: ...considerations related to operation maintenance and management must be taken such as duplicating the system and emergency power generation facilities Observe the contents of this manual such as the us...

Page 3: ...wed when using the UPS and batteries 2 SYMBOL Power output ON OFF switch 3 INTERNAL BATTERY Internal battery voltage is 12V DC FOR BY35S BY50S BY80S BY120S 4 TEMPERATURE RATING The maximum ambient tem...

Page 4: ...tents Page 1 Perform installation and connection Page 6 Check the operation and displays Pages 12 Charge the battery Page 13 Measure the backup time Page 28 Read Using the UPS monitoring software Page...

Page 5: ...p procedures and basic operation 17 3 3 Interpreting beeps and displays 20 4 UPS functions 22 4 1 Suspending a beep 22 4 2 Self diagnosis test 22 4 3 Description of the auto battery test function 23 4...

Page 6: ...lications with the same level of importance Warning Important information for safe operation is described Be sure to read it before installation and start of use Misuse may cause injury or property da...

Page 7: ...or environmental conditions during use storage Do not install or store the unit in the places listed below Do not store in places where the humidity is lower than 10 or higher than 90 Do not use the u...

Page 8: ...ower supply output receptacles Accumulated dust may cause a fire Do not use the unit in a closed place and do not cover the unit Doing so may cause abnormal heating or a fire If you notice abnormal so...

Page 9: ...t doing so could cause injury or burns due to liquid acid leakage Use a specified battery for replacement Not doing so may cause a fire Product model BYB50S for BY35S BY50S BYB80S for BY80S and BYB120...

Page 10: ...the unit The unit repeatedly and frequently switches between Commercial Power Mode and Battery Mode which may shorten the life of the battery The page printer has a large peak current so an excess of...

Page 11: ...months the internal timer is reset and the scheduled operation does not start Note that this period reduces to approximately half when the battery is dead If a period of 3 months is exceeded you start...

Page 12: ...age contents are included and there is no damage found on their appear ance If you should notice defects or anything wrong contact us ____ BY35S BY50S BY80S BY120S Instruction manual Japanese and Engl...

Page 13: ...1 3 Name of each part B C D BY35S BY50S BY80S BY120S A Status indicator digital display B Battery replacement lamp C Beep stop test switch D Power switch A Status indicator digital display B Battery r...

Page 14: ...BY35S BY50S BY80S BY120S 1 3 Bottom view BY35S BY50S A Fixation screw for battery replacement cover B Battery replacement cover A B...

Page 15: ...cable E Power supply output receptacles A USB connector B Setting switch C AC input overcurrent protection switch D AC input cable E Power supply output receptacles A USB connector B Setting switch C...

Page 16: ...BY35S BY50S BY80S BY120S 1 5 1 4 Explanation of symbols used on unit Symbol Description Power output ON OFF switch Suspend a beep Batteries at end of useful life necessary to replace the batteries...

Page 17: ...ct devices such as dryers some solenoid valves etc which have a half wave rectifier that allows only half cycle AC power to flow through Overcurrent may damage the UPS Connect the unit to a wall outle...

Page 18: ...ng of the plug strip heats up which may cause a fire Do not pinch or tie the cable of the unit Doing so may cause the cable to be damaged or heated which may cause an electric shock or a fire If the c...

Page 19: ...ect a page printer such as a laser printer to the unit The unit repeatedly and frequently switches between Commercial Power Mode and Battery Mode which may shorten the life of the battery The page pri...

Page 20: ...contacting us about the device Check the unit s serial number inscribed on the back of the unit or printed on the attached serial number label Correct Positions BY35S BY50S BY80S BY120S Incorrect Pos...

Page 21: ...4 Maximum screw length 12 mm Maximum tightening torque 1 57 N m Proper Positions Horizontal Vertical Attach the unit to the base plate by threading 4 screws through the temporary screw holes on the un...

Page 22: ...commercial power Router or other peripheral PC Example of connection 1 Example of connection 2 A 2 pin input plug of a connecting device can be connected to the power supply output receptacle whithou...

Page 23: ...rom commercial power Status indicator Description Power switch ON Operating normally 2 Bring all the connected devices into operation Including devices connected to the AC outlet of your PC Operate th...

Page 24: ...o 4 on page 12 If the problem persists after checking the 2 points above contact us ____ See also Setting switch 1 can be used to turn the beeper ON OFF Page 24 6 Connect the AC input plug to a wall o...

Page 25: ...rging the battery 2 7 Recharging the battery 2 6 Measuring the initial value of backup time When you measure the backup time initial value of the unit in your environment this value can be used as a g...

Page 26: ...plug from a wall outlet commercial power Using the unit under such conditions may cause a fire If the unit becomes wet immediately stop using it unplug the AC input cable and contact us at __________...

Page 27: ...ect whether or not auto restart is performed See Page 24 Scheduled operation using the UPS monitoring software When performing scheduled operation in which the UPS is stopped and a device such as a br...

Page 28: ...setting Input power sensitivity setting page 25 The status indicator displays and the self diagnostic test is performed in Battery Mode for about 10 seconds If the battery voltage is low the self dia...

Page 29: ...ing switch 1 can be used to turn the beeper ON OFF Page 24 indicates blinking Status indicator Battery replacement Beep Output Charging Description Solution Intermittent 4 second intervals ON OFF Disc...

Page 30: ...te ly and power output is stopped the UPS restarts automatically and resumes power output The expended battery begins to charge See also Setting switch 2 can be used to select whether or not auto rest...

Page 31: ...de due to power failure or AC input error Output will stop if Battery Mode continues Same as above Battery level is low so output will soon stop Battery is dead so output stopped This is displayed onl...

Page 32: ...ve Output stopped due to an internal communication error Continuous 27 Same as above Output stopped due to battery charge voltage error under Output stopped due to problem with the internal temperatur...

Page 33: ...tatus indicator No beep sounds After about 10 seconds when the test is complete the normal operation automatically starts 3 If the status indicator battery replacement lamp blinks and the beeper sound...

Page 34: ...cribed in 4 Displays and beeps when there is an equipment failure and 5 Display and beep for battery replacement ON DIP 1 2 5 6 7 8 3 4 Setting switch ON ON side OFF side 1 Selecting functions with th...

Page 35: ...t automatically starts and begins to output when the commercial power is restored ON Does not automatically start when power is restored After the unit is shut down with the UPS monitoring software it...

Page 36: ...re quency the last time there was AC input When using the cold start function When performing operation with cold start a second time turn OFF the power switch and wait at least 20 seconds before turn...

Page 37: ...d OFF the setting mode quits and the unit enters power switch OFF status status 2 2 Settings ON Cold start ON mode C 1 C D D D A B OFF Cold start OFF mode Factory shipped setting C 1 C D D D 1 Display...

Page 38: ...ble 1 Complete beep stop 2 Output voltage setting 3 Voltage sensitivity mode setting 4 Cold start setting 5 Maximum backup time setting 6 Automatic self diagnostic testing 7 Startup delay time setting...

Page 39: ...e value in the right table for conversion When the power factor is unknown enter 1 The power factor usually ranges between 0 6 and 1 Indica tion Value VA power factor W A power factor 100 W 1 When the...

Page 40: ...rence only Times may vary according to battery life and external environmental conditions temperature etc Power consumption of connected devices W Minutes Backup time BY120S BY80S BY35S BY50S 140 120...

Page 41: ...hen you mea sured the initial value to make judgment accurately When maintaining the connected equipment turn OFF the power switch and disconnect the AC input plug Even if you disconnect the AC input...

Page 42: ...battery may explode or leak dilute sulfuric acid Do not use a new battery and an old battery at the same time Dilute sulfuric acid may leak The battery can be replaced while the unit is stopped power...

Page 43: ...e the top Remove the one fixation screw one of the battery replacement cover using a screwdriver turn counter clockwise 2 Slide the battery replacement cover upward to remove the cover Battery recycli...

Page 44: ...ry by the left hand holding the battery by the right hand If it is hard to remove move the connector up and down with your fingers or long nose pliers to pull out Pull out the battery cable black from...

Page 45: ...il they click Hold the battery by the right hand and insert the connector of the battery cable red into the terminal by the left hand Hold the battery by the right hand and insert the connector of the...

Page 46: ...a wall outlet commercial power and turn ON the power switch of the UPS When operation starts the self diagnostic test is automatically performed Nor mal operation resumes after the 10 second test Aft...

Page 47: ...remove the 2 screws Detach the front panel Pull the front panel upward a little if the front panel is hard to detach 2 Disconnect the battery connector and remove the metal cover Remove the red and b...

Page 48: ...t the new battery pack You may hear a pop sound when you connect the battery if it is replaced after the unit s operation is stopped but this is not abnormal Fit the metal cover into the grooves and s...

Page 49: ...attery when operation was stopped Connect the AC input plug to a wall outlet commercial power and turn ON the power switch of the UPS When operation starts the self diagnostic test is automatically pe...

Page 50: ...cause deformation or discoloration 2 Removing dust from the AC input plug power supply output receptacles of the UPS Stop all the connected devices and the UPS and disconnect the AC input plug from a...

Page 51: ...munication method UPS monitoring software Reference BY35S BY50S BY80S BY120S Windows 7 Windows Vista Windows Server 2008 including R2 Windows Server 2003 including R2 x64 Edition Windows XP x64 Editio...

Page 52: ...PowerAct Pro 4 x Compatible OS Windows 7 Windows Vista Windows Server 2008 including R2 Windows Server 2003 including R2 x64 Edition Windows XP x64 Edition Windows Server 2003 including R2 Windows XP...

Page 53: ...at shutdown items such as application programs can be launched 10 Event log save Information of events that occur on the UPS power supply problems setting changes occurrences of failure etc are saved...

Page 54: ...8 For more information and operation refer to the Quick Installation Guide for UPS Monitoring Software and the online help in the included CD ROM 7 1 When using the included UPS monitoring software to...

Page 55: ...the UPS monitoring software To manually start up this unit after it has been stopped by a scheduled operation turn OFF the power switch and turn it back ON again To stop the unit when it is in operat...

Page 56: ...he included UPS service driver on the computer Software to install UPS service driver How to install Refer to the separate UPS monitoring software installation guide USB USB BY35S BY50S BY80S BY120S I...

Page 57: ...nt that consumes large power This problem may occur also when you connect many devices to a plug strip or extension cord connected to the UPS if it is a long or thin cable Does not turn ON when power...

Page 58: ...ine wave sine wave Waveform distortion rate In Battery Mode 25 or less Output receptacle NEMA 5 15R x 4 receptacles Switching time 10 msec max Battery Backup time 2 6 min or more 3 5 min or more 4 min...

Page 59: ...8 B Dimensions BY35S BY50S 165 0 5 92 1 285 1 Unit mm Dimensions are not including the height of the rubber feet The height of the rubber feet is about 0 8 mm and the height including the rubber feet...

Page 60: ...50S BY80S BY120S 49 BY80S Unit mm Dimensions are not including the height of the rubber feet The height of the rubber feet is about 1 6 mm and the height including the rubber feet is 236 6 mm 235 1 85...

Page 61: ...erences 50 BY120S Unit mm 328 5 1 90 1 298 1 Dimensions are not including the height of the rubber feet The height of the rubber feet is about 1 6 mm and the height including the rubber feet is 299 6...

Page 62: ...uct Models BY35S BY50S BY80S BY120S Replacement battery pack BYB50S BYB80S BYB120S Bracket BYP50S BYP80S Charging circuit 100 VAC input AC input overcurrent protection DC DC converter Battery Inverter...

Page 63: ...No part or whole of this manual may be reproduced without permission The contents of this manual are subject to change without notice OMRON Corporation K1L D 09007C 9475019 3B...

Reviews: