4
.
UPS functions
24
●
Setting for beeper sound in the event of power failure, etc. (setting switch
1
)
… Factory setting: OFF
OFF: The beeper sounds when an alarm is necessary.
ON: The beeper does not sound for backup operation or battery replacement. The beeper
sounds for other errors (connection capacity exceeded, operation error, etc.).
ON
ON
DIP
1 2
5
6
7
8
3 4
●
Auto startup setting after recovery from power failure (setting switch
2
)
… Factory setting: OFF
OFF: Automatically starts when power is restored.
After a power failure occurs and the unit shuts down with the UPS monitoring software, the
unit automatically starts and begins to output when the commercial power is restored.
ON: Does not automatically start when power is restored.
After the unit is shut down with the UPS monitoring software, it does not start up when com-
mercial power is restored. Startup is performed by turning the power switch OFF once,
and then back ON again.
1 2
5
3 4
8
6 7
ON
ON
DIP
●
Setting for whether or not to perform battery test (setting switch
3
)
… Factory setting: OFF
OFF: The battery test is automatically executed once every 4 weeks.
ON: Does not perform the auto battery test.
Use this setting to disable Battery Mode for for the regularly performed auto battery test.
1 2
5
3 4
8
6 7
ON
ON
DIP
Setting switch
4
to
8
Factory-shipped setting: OFF
These switches are not used in BY35S/BY50S/BY80S/BY120S.