6
Safety precautions
Do not wet or pour water onto the unit.
●
Doing so may cause an electric shock or a fire.
●
If you wet the unit, stop using it and the unit must be inspected and/or repaired.
For repair, contact us; ____
When the battery is dead, replace it immediately or stop using the unit.
●
Continuing the use of it may cause a fire.
Wipe the 100-VAC input plug clean of dirt with a dry cloth occasionally.
●
Settled dust may cause a fire.
Caution
(for use)
* The values in the table are the expected life under standard
use conditions and are not guaranteed.
Ambient temperature
20
°
C
30
°
C
Expected life
4 to 5 years
2 to 2.5 years
Caution
(for installation and connection)
Do not pinch or tie the cable of the unit.
●
Doing so may cause the cable to be damaged or heated, which may cause an electric shock
or a fire.
●
If the cable is damaged, stop using the unit and the cable must be repaired.
For repair, contact us; ____
All of the included accessories are designed to be used exclusively with
the unit. Do not use the accessories with other devices.
●
Doing so may compromise the safety of devices.
●
This UPS utilizes voltages that may be hazardous. Do not attempt to disassemble the unit. The
unit contains no user serviceable parts. Only factory service personnel may perform repairs.
●
Connection to any other type of receptacle other than a two-pole, three-wire grounded
receptacle may result in shock hazard as well as violate local electical codes.
●
Do not allow liquids or any foreign object to enter the UPS. DO not place beverages or any
other liquid-containing vessels on or near the unit.
●
This unit intended for installation in a controlled environment (temperature controlled, indoor
area free of conductive contaminants). Avoid installing the UPS in locations where there is
standing or running water, or excessive humidity.
●
Do not attach a power strip or surge suppressor to the UPS.
●
Do not attach non-computer-related items, such as medical equipment, life-support equipment,
microwave ovens, or vacuum cleaners to UPS.
●
With the installation of the equipment it should be prevented, that the sum of the leakage
current of the UPS and the connected consumer does not exceed 3.5mA.
●
For PLUGGABLE EQUIPMENT, the socket-outlet shall be installer near the equipment and
shall be easily accessible.