12
PROFIBUS DP Gateway
Section 1-3
Protocol Specifications
Item
Specification
Pr
ot
o
c
ol
po
rt
ph
y
s
ic
al
l
a
y
e
r
Media types
• RS-422A, galvanically isolated.
• RS-485, galvanically isolated.
Selection for RS-485 is made with Physical layer switch 1 (see
2-1-3
Switch Settings).
ON:
RS-485
OFF:
RS-422A
termination resistor
Internal 220 Ohm resistor between receiver lines.
Use of resistor can be enabled or disabled, using Physical layer switch
2 (see
2-1-3 Switch Settings).
ON:
Termination resistor enabled.
OFF:
Termination resistor disabled.
Connector
5-pin Phoenix connector
Baud rates supported
• 9.6 kbit/s
• 19.2 kbit/s
• 38.4 kbit/s
Selection via DIP-switches 1 and 2. (See
2-1-3 Switch Settings).
Protocol types supported via this port
• Compoway-F
• Host Link
• K-Format
• Memobus
Device address range
1
~ 15, set through the slot number of the PROFIBUS module configu-
ration. Number 0 (zero) is reserved.
A
u
xi
liar
y por
t
Media type
RS-232C, located behind cover marked “Peripheral”
Use the CS1W-CN226 connection cable for connecting the PRT1-
SCU11 with Thermotools
Baud rates supported
Baud rate used on Auxiliary port is the same as the baud rate used on
the main protocol port.
Selection via DIP-switches 1 and 2. (See
2-1-3 Switch Settings).
Protocol types supported via this port
• Compoway-F
• K-Format
• Memobus
PR
O
F
IB
US DP i
n
te
rf
ac
e
Applicable standards
EN50170, Volume 2
Protocol type supported
PROFIBUS DP
PROFIBUS Unit type
PROFIBUS DP slave
PROFIBUS Media type
RS-485, galvanically isolated
PROFIBUS Connector
9-pin sub-D female connector (#4/40 UNC thread)
Termination according to EN50170 provided by the cable connector
Unit device address range
0
~ 99, set through rotary switches
Remote setting not supported.
Baud rates supported (Auto-detect)
• 9.6 kbit/s
• 19.2 kbit/s
• 45.45 kbit/s
• 93.75 kbit/s
• 187 kbit/s
• 500 kbit/s
• 1.5 Mbit/s
• 3 Mbit/s
• 6 Mbit/s
• 12 Mbit/s
Summary of Contents for PROFIBUS DP GATEWAY
Page 1: ...OPERATION MANUAL PROFIBUS DP Gateway to Host Link Compoway F PRT1 SCU11 Cat No W01E EN 02 ...
Page 2: ...PRT1 SCU11 PROFIBUS DP Gateway Operation Manual Revised September 19 2005 ...
Page 3: ...iv ...
Page 15: ......
Page 31: ......
Page 71: ......
Page 77: ......
Page 81: ......