54
Auxiliary RS-232C interface
Section 3-8
3-8
Auxiliary RS-232C interface
The PRT1-SCU11 provides an RS-232C interface, behind a cover lid on the
front of the Unit. This interface allows a user to connected an IBM compatible
computer with a serial port and send and receive data to a Compoway-F, or K-
Format device using the software package CX-Thermo.
Equally, when Memobus has been selected as the protocol, the RS-232C
interface can be used to transfer commands from CX-Drive and the Varispeed
F7 Inverter.
Using CX-Thermo
Before using CX-Thermo DIP-switch 4 must be set on, a group of four DIP-
switches is located on the front of the PRT1-SCU11 Unit.
Note CX-Thermo is not shipped with the PRT1-SCU11.
!WARNING
When DIP-switch 4 is switched on, the PRT1-SCU11 will stop the data
exchange with the PROFIBUS Master. The PROFIBUS DP interface will stay
inactive until switch 4 is switch off.
When DIP-switch 4 is set on:
• The diagnostics indicates Slave Not_Ready.
• FERR LED is switched off.
• COMM LED starts flashing.
• FCOM start flashing.
• BF LED is switched off.
To connect with the PRT1-SCU11 use an auxiliary RS-232C compatible inter-
face on an IBM compatible computer and a standard Omron RS-232C PLC
cable e.g. (CS1W-CN226).
Note The interface connection is not galvanically isolated.
The baud rate settings are the same as used for the Compoway-F interface,
as set through the associated DIP-switches.