65
Memory Mapping
Appendix A
A-3
Parameter / Command Mapping for Memobus Devices
The table below lists the Mapping of individual parameters in the Fixed and Flexible I/O blocks on to the OYMC
Varispeed F7 Inverter. Refer to the F7 Inverter’s Operation Manual (YEG-TOE-S616-55.1-OY) for more infor-
mation
.
Note Being able to write to the voltage register, a special firmware version - VSF108981 - for the Varispeed F7
Inverter is required. Contact your supplier on how to obtain this firmware upgrade.
Parameter
Read/
Write
Register Number
(Hex)
Remarks
F
ix
e
d
bl
ock
Command register
W
0001
Frequency register
W
0002
Voltage register
W
0003
See Note
Status register
R
0020
Frequency register
R
0023
Voltage register
R
0025
Fl
e
x
ib
le
b
loc
k
Write register 1
W
0000 ~ FFFF
The registers to read/write can be selected by the user
when setting up the PROFIBUS I/O configuration.
An invalid register address selection (i.e. non-existent or
read-only) will result in a Memobus error.
Write register 2
W
0000 ~ FFFF
Write register 3
W
0000 ~ FFFF
Read register 1
R
0000 ~ FFFF
Read register 2
R
0000 ~ FFFF
Read register 3
R
0000 ~ FFFF