45
Compoway-F communication
Section 3-3
!WARNING
When DIP-switch 4 is switched on, the Gateway Unit will stop the data
exchange with the PROFIBUS master. The PROFIBUS-DP interface will stay
inactive until switch 4 is switch off.
When DIP-switch 4 is set on:
• The diagnostics indicates Slave Not_Ready.
• FERR LED is switched off.
• COMM LED starts flashing.
• FCOM start flashing.
• BF LED is switched off.
To connect with the Gateway use an auxiliary RS-232C compatible interface
on an IBM compatible computer and a standard Omron RS-232C PLC cable
e.g. (CS1W-CN226).
Note
The interface connection is not galvanically isolated.
The baud rate settings are the same as used for the Compoway-F interface,
as set through the associated DIP-switches.
To connect with the unit use the second button in the menu, starting from the
left, see figure below.
When connected with CX-Thermo you can configure the required TC. For
detailed information please use the ThermoTool online help and read the
manual of the used Temperature Controller.