SIEPCYEUOQ2V01A Q2V Technical Manual
125
Input Data
Parameter
Unit
Auto-Tuning Mode
(T1-01 Setting)
Rotational Auto-Tuning
(0)
Stationary Auto-Tuning
1
(1)
Stationary Line-Line
Resistance
(2)
Test Mode Selection
T1-12
-
-
x
-
No-load Voltage
T1-13
V
x
x
-
*1
Shows 0 Hz as the default value. If you do not know the Motor Rated Slip Frequency, keep the setting at 0 Hz.
*2
Input this value when
A1-02 = 0 [Control Method = V/f Control]
.
*3
If
T1-12 = 1 [Test Mode Selection = Yes]
, when you run the motor in Drive Mode for the first time after Auto-Tuning, the drive will
automatically set
E2-02 [Mot Rated Slip]
and
E2-03 [Mot No-Load Current]
.
*4
Input this value when
T1-10 [Motor Rated Slip Frequency] = 0 Hz
.
◆
Auto-Tuning for PM Motors
This section gives information about Auto-Tuning for PM motors. Auto-Tuning sets motor parameters
E1-xx and
E5-xx
.
Table 4.9 Auto-Tuning for PM Motors
Mode
Parameter
Settings
Application Conditions and Benefits
Applicable Control Method
(A1-02 Setting)
PM OLVector
(5)
PM AOLVector
(6)
Manual Entry w/ Motor
Data Sheet
T2-01 = 0
•
When the information from the motor test report or motor nameplate is available.
•
Rotational/Stationary Auto-Tuning that energizes the motor is not done. Manually
input the necessary motor parameters.
x
x
PM Stationary Auto-
Tuning
T2-01 = 1
•
When the information from the motor test report or motor nameplate is not available.
Note:
With Stationary Auto-Tuning, the energized drive stays stopped for approximately 1
minute. During this time, the drive automatically measures the necessary motor
parameters.
x
x
PM Stationary Auto-
Tuning for Stator
Resistance
T2-01 = 2
•
After Auto-Tuning, the wiring distance between the drive and motor changed by 50 m
(164 ft) or more.
•
When the motor output and drive capacity are different.
x
x
PM Motor Code
Selection
T2-01 = 4
•
When the information from the motor test report or motor nameplate is not available.
•
When you can decouple the motor and load and the motor can rotate freely while Auto-
Tuning.
•
The drive will automatically set the values measured during Auto-Tuning to the motor
parameters.
x
x
High Frequency
Injection
T2-01 = 5
•
Automatically sets the control parameters that are necessary to set
n8-35 = 2
[InitRotorPos Selection = ]
or
n8-57 = 1 [High-Freq Injection = Enabled]
.
•
Applicable to IPM motors only.
•
Do Auto-Tuning with the motor connected to the drive.
Note:
When you set
n8-35 = 1
or
n8-57 = 1
, do High Frequency Injection Auto-Tuning. Set
the data on the motor nameplate to the drive before you do High Frequency Injection
Auto-Tuning. In High Frequency Injection Auto-Tuning, the drive energizes the
stopped motor and automatically adjusts the parameters.
x
x
■
Input Data for PM Motor Auto-Tuning
To do Auto-Tuning, input data for these items that have an "x". Before starting Auto-Tuning, prepare the motor
test report or record the information on the motor nameplate as a reference.
Table 4.10 Input Data for PM Motor Auto-Tuning
Input Data
Parameter
Unit
Auto-Tuning Mode
(T2-01 Setting)
PM Motor Parameter Settings
(0)
PM Static Full
AutoTune
(1)
PM Static R Autotune
(2)
Control Method Selection
A1-02
-
5, 6
5
6
5
6
5, 6
PM Motor Code Selection
T2-02
-
Motor code of Yaskawa
motor
FFFF
FFFF
-
-
-
PM Motor Type
T2-03
-
-
-
-
x
x
-
PM Motor Rated Power
T2-04
kW
-
x
x
x
x
-
PM Motor Rated Voltage
T2-05
V
-
x
x
x
x
-
PM Motor Rated Current
T2-06
A
-
x
x
x
x
x
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...