130
SIEPCYEUOQ2V01A Q2V Technical Manual
4.10
Test Run
After you set the basic parameters and do Auto-Tuning, do a test run.
WARNING!
Crush Hazard. Test the system to make sure that the drive operates safely after you wire the drive and set
parameters. If you do not test the system, it can cause damage to equipment or serious injury or death.
◆
No-Load Test Run
Before connecting the motor to the machine, make sure that you check the operation status of the motor.
■
Precautions before Operation
Before rotating the motor, check these items:
•
Check for safety issues near the drive, motor, and machine.
•
Make sure that all emergency stop circuits and machine safety mechanisms are operating correctly.
■
Items to Check before Operation
Check these items before operation:
•
Is the motor rotating in the forward direction?
•
Is the motor rotating smoothly (no unusual sounds or unusual vibrations)?
•
Does the motor accelerate/decelerate smoothly?
◆
Do a No-Load Test Run
Do these steps for a no-load test run:
1.
Energize the drive, or push
to show the frequency reference screen.
2.
Push
to illuminate the LOCAL/REMOTE LED.
3.
Use
/
/
/
to set
d1-01 = 6.00 [Reference 1 = 6.00 Hz]
, then push
.
4.
Push
.
The RUN indicator illuminates, and the motor runs at 6.00 Hz in the forward direction.
5.
Make sure that the motor is rotating in the correct direction and that the drive does not show a fault.
If the drive detects a fault, remove the cause.
A - Forward Rotation of Motor (Counter Clockwise Direction as Seen from
Load Shaft)
6.
Push
to increase the frequency reference value.
Change the setting value in increments of 10 Hz if necessary and examine the response.
Ex.: 6 Hz → 20 Hz → 30 Hz → 40 Hz → 50 Hz → 60 Hz
7.
Each time you increase the setting value, use
U1-03 [Output Current]
to check the drive output current.
When the output current of the drive is not more than the motor rated current, the status is correct.
8.
Make sure that the motor rotates correctly, then push
.
The RUN LED flashes and goes off when the motor stops completely.
◆
Actual-Load Test Run
Test the operation without a load, then connect the motor and machine to do a test run.
■
Precautions before Operation
Before rotating the motor, check these items:
•
Check for safety issues near the drive, motor, and machine.
•
Make sure that all emergency stop circuits and machine safety mechanisms are operating correctly.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...