136
SIEPCYEUOQ2V01A Q2V Technical Manual
4.12
Test Run Checklist
Examine the items in this checklist and check each item before a test run.
Checked
No.
Description
1
Correctly install and wire the drive as specified by this manual.
2
Energize the drive.
3
Set the voltage for the power supply in
E1-01 [Input AC Supply Voltage]
.
Check the applicable items as specified by your control method.
WARNING!
Sudden Movement Hazard. Correctly wire the start/stop and safety circuits before you energize the drive. If you
momentarily close a digital input terminal, it can start a drive that is programmed for 3-Wire control and cause serious injury or
death from moving equipment.
Table 4.22 V/f [A1-02 = 0]
Checked
No.
Description
4
Select the best V/f pattern for your application and motor characteristics.
Example: For a motor with a rated frequency of 60 Hz, set
E1-03 = 1 [V/f Pattern Selection = CT_60-60Hzmax]
as a standard V/f pattern.
Table 4.23 OLV [A1-02 = 2]
Checked
No.
Description
5
Decouple motor shafts and machines.
6
Refer to the information on the motor nameplate and set this data correctly:
•
Motor rated power (kW) to
T1-02
•
Motor rated voltage (V) to
T1-03
•
Motor rated current (A) to
T1-04
•
Motor base frequency (Hz) to
T1-05
•
Number of motor poles to
T1-06
•
Motor base speed (min
-1
) to
T1-07
7
Do Rotational Auto-Tuning.
Table 4.24 OLV/PM [A1-02 = 5]
Checked
No.
Description
8
Set
E5-01 through E5-24 [PM Motor Settings]
.
Table 4.25 AOLV/PM [A1-02 = 6]
Checked
No.
Description
9
Set
E5-01 through E5-24 [PM Motor Settings]
.
10
Set
C5-01 [ASR PGain 1] and C5-02 [ASR ITime 1]
.
Checked
No.
Description
11
Make sure that the keypad shows READY LED before you start to operate the motor.
12
To give the Run command and frequency reference from the keypad, push
to set to LOCAL Mode (when in LOCAL Mode, the LO/RE
LED illuminates).
13
If the motor rotates in the opposite direction during test run, switch two of the motor cables (U/T1, V/T2, W/T3).
14
Set Heavy Duty or Normal Duty Mode with
C6-01 [ND/HD Duty Selection]
to conform to the load condition.
15
Set
E2-01 [Mot Rated Current (FLA)] and L1-01 [Motor Cool Type for OL1 Calc]
correctly for motor thermal protection.
16
Set the drive for REMOTE Mode when the control circuit terminals supply the Run command and frequency reference (in REMOTE Mode, the
LO/RE LED turns OFF).
17
When you use terminal AI1 for the frequency reference:
•
Set
H3-01 = 0, 1 [AI1 Signal Level Select = 0 to 10V (Lower Limit at 0), 0 to +10 V (Without Lower Limit)]
.
•
Set
H3-02 = 4 [AI1 Function Selection = Freq Ref/BIAS]
.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...