168
SIEPCYEUOQ2V01A Q2V Technical Manual
WARNING!
Electrical Shock Hazard. Make sure that the protective ground wire conforms to technical standards and local
safety regulations. The IEC/EN 61800-5-1:2007 standard specifies that you must wire the power supply to automatically de-
energize when the protective ground wire disconnects. If you turn on the internal EMC filter, the leakage current of the drive will
be more than 3.5 mA. You can also connect a protective ground wire that has a minimum cross-sectional area of 10 mm
2
(copper wire). If you do not obey the standards and regulations, it can cause serious injury or death.
WARNING!
Electrical Shock Hazard. Only connect peripheral options, for example a DC reactor or braking resistor, to terminals
+1, +2, -, B1, and B2. Failure to obey can cause serious injury or death.
Note:
•
The recommended wire gauges are based on drive continuous current ratings with 75 °C (167 °F) 600 V class 2 heat-resistant indoor
PVC wire. Assume these conditions:
–
Ambient temperature: 40 °C (104 °F) maximum
–
Wiring distance: 100 m (3281 ft) maximum
–
Normal Duty rated current value
•
Refer to the instruction manual for each device for recommended wire gauges to connect peripheral devices or options to ter1,
+2, -, B1, and B2. Contact the manufacturer or your nearest sales representative if the recommended wire gauges for the peripheral
devices or options are out of the range of the applicable gauges for the drive.
Three-Phase 200 V Class (UL Compliance)
Model
Terminal
Recommended
Gauge
AWG, kcmil
Applicable Gauge
AWG, kcmil
Wire
Stripping
mm
Terminal Screw
Tightening Torque
N
∙
m (in
∙
lb)
Size
Shape
2001
R/L1, S/L2, T/L3
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
14
-
M3.5
0.8 - 1.0
(7.1 - 8.9)
2002
R/L1, S/L2, T/L3
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
14
-
M3.5
0.8 - 1.0
(7.1 - 8.9)
2004
R/L1, S/L2, T/L3
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
14
-
M3.5
0.8 - 1.0
(7.1 - 8.9)
2006
R/L1, S/L2, T/L3
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
U/T1, V/T2, W/T3
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
-, +1, +2
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
B1, B2
14
14
6.5
M3
0.5 - 0.6
(4.4 - 5.3)
14
-
M3.5
0.8 - 1.0
(7.1 - 8.9)
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...