SIEPCYEUOQ2V01A Q2V Technical Manual
177
Drive Model
Maximum Applicable Motor Output
kW (HP)
Time Delay Fuse
Semiconductor Protection Fuse Rated Current
Manufacturer: EATON/Bussmann
ND
HD
Class J, CC, and T Fuse
Rated Current
A
Model
Input Rated Current
A
4023
11.0 (15)
7.5 (10)
-
FWH-100B
100
4031
15.0 (20)
11.0 (15)
-
FWH-125B
125
4038
18.5 (25)
15.0 (20)
-
FWH-175B
175
4044
22.0 (30)
18.5 (25)
-
FWH-200B
200
4060
30.0 (40)
22.0 (30)
-
FWH-200B
200
◆
Low Voltage Wiring for Control Circuit Terminals
You must provide low voltage wiring as specified by the National Electric Code (NEC), the Canadian Electric
Code, Part I (CEC), and local codes. The manufacturer recommends the NEC class 1 circuit conductor. Use the
UL approved class 2 power supply for external power supply.
Table 5.18 Control Circuit Terminal Power Supplies
Input/Output
Terminals
Power Supply Specifications
Digital input
DI1 to DI7, D0V, DIC, D24V
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power supply.
Analog input
AI1, AI2, A0V ,+10V
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power supply.
Analog output
AO, A0V
Uses the LVLC power supply in the drive.
Pulse train output
PO, A0V
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power supply.
Pulse Train Input
PI, A0V
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power supply.
Safe disable input
H1, H2, HC
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power supply.
Serial communication input/output
RS485+, RS485-, A0V
Uses the LVLC power supply in the drive.
Use the UL Listed class 2 power supply for external power supply.
24 V external power supply
D24V, A0V
Use the UL Listed class 2 power supply.
◆
Drive Motor Overload and Overheat Protection
The drive motor overload and overheat protection function complies with the National Electric Code (NEC) and
the Canadian Electric Code, Part I (CEC).
Set the Motor Rated Current and
L1-01 through L1-04 [Motor Overload Protection Select]
correctly to enable
motor overload and overheat protection.
Refer to the control method and set the motor rated current with
E2-01 [Mot Rated Current (FLA)]
,
E5-03 [PM
Mot Rated Current (FLA)]
, or
E9-06 [Motor Rated Current]
.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...