180
SIEPCYEUOQ2V01A Q2V Technical Manual
5.6
Safe Disable Input
This section gives precautions to support the Safe Disable input. Contact the manufacturer for more information.
Figure 5.20 TUV Mark
The TUV mark identifies that the product complies with the safety standards.
The safety function complies with the following standards.
Table 5.21 Applied Safety Standards and Unified Standards
Safety Standards
Unified Standards
Functional Safety
IEC/EN 61508:2010 (SIL3)
IEC 62061:2005/AMD2:2015 (SILCL3)
EN 62061:2005/A2:2015 (SILCL3)
IEC 61800-5-2:2016 (SIL3)
EN 61800-5-2:2017 (SIL3)
Machine Safety
ISO/EN ISO 13849-1:2015 (Cat.3, PL e)
EMC
IEC 61000-6-7:2014
EN 61000-6-7:2015
IEC/EN 61326-3-1:2017
LVD
IEC 61800-5-1:2007/AMD1:2016
EN 61800-5-1:2007/A1:2017
Note:
SIL = Safety Integrity Level.
◆
Safe Disable Specifications
The Safe Disable input provides the stop function that complies with
“
Safe Torque Off
”
as specified by IEC/EN
61800-5-2. The Safe Disable input meets the requirements of ISO/EN ISO 13849-1 and IEC/EN 61508. It also has
a safety status monitor to detect safety circuit errors.
When you install the drive as a component in a system, you must make sure that the system complies with the
applicable safety standards.
Table 5.22 Safe Disable Specifications
Item
Description
Input/Output
•
Input: 2
Safe Disable input (H1, H2)
Signal ON level: 18 Vdc to 28 Vdc
Signal OFF level: -4 Vdc to +4 Vdc
•
Output: 1
MFDO safety monitor output for external device monitor (EDM)
Response time from when the input opens to when the drive output stops
3 ms or less
Response time from when the H1 and H2 terminal inputs open to when the EDM signal
operates
30 ms or less
Failure probability in Less frequent operation request mode
PFD = 1.38E
-5
Failure probability in Frequent operation request mode or continuous mode
PFH = 3.35E
-9
Performance level
The Safe Disable input complies with the performance level requirements of EN ISO
13849-1.
HFT (hardware fault tolerance)
N = 1
Type of subsystem
Type B
MTTF
D
High
DCavg
Medium
Mission time
10 years
EDM = External Device Monitoring
PFD = Probability of Failure on Demand
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...