SIEPCYEUOQ2V01A Q2V Technical Manual
201
Table 6.10 Modbus Communications Command Data
Register No. (Hex.)
Description
0000
Reserved
0001
Run command, multi-function input command
bit 0
When
H5-12 = 0
, Forward run/stop
1: Forward run, 0: Stop
When
H5-12 = 1
, run/stop
1: Run, 0: Stop
bit 1
When
H5-12 = 0
, Reverse run/stop
1: Reverse run, 0: Stop
When
H5-12 = 1
, Forward/Reverse run
1: Reverse, 0: Forward run
bit 2
External fault
1: EF0 [Option Card External Fault]
bit 3
Fault Reset
1: Reset command
bit 4
Multi-function input 1
When the multi-function input command is
H1-01 =
1 [Forward Run]
, bit 4 is
“
ComRef.
”
Note:
When you switch the bit ON as ComRef, the
frequency reference source changes to Modbus
communications. When you connect a
communication option to the drive, the
frequency reference source gives priority to the
communications option.
bit 5
Multi-function input 2
When the multi-function input command is
H1-02 =
2 [Reverse Run]
, bit 5 is
“
ComCtrl.
”
Note:
When you switch the bit ON as ComCtrl, the
Run Command source changes to Modbus
communications. When you connect a
communication option to the drive, the Run
Command source gives priority to the
communications option.
bit 6
Multi-function input 3
bit 7
Multi-function input 4
bit 8
Multi-function input 5
bit 9
Multi-function input 6
bit A
Multi-function input 7
bit B -
F
Reserved
0002
Fre
quency
Refer
ence
o1-03 [FrqDisplay Unit Selection]
(unsigned) sets
the units.
0003
Output
voltage
gain
Units: 0.1%
Setting range: 20 (2.0%) to 2000 (200.0%), the
default value at energize: 1000 (100.0%)
0004
Torque limit (0.1% signed)
0005
Torque compensation (0.1% signed)
0006
PID setpoint (0.01% signed)
0007
Setting for the multi-function analog monitor output terminal
AO (10 V/4000 (Hex.))
0008
Reserved
Register No. (Hex.)
Description
0009
MFDO setting
bit 0
MFDO (terminal NO-CM)
1: ON, 0: OFF
bit 1
Multi-function photocoupler output 1 (terminal
DO1-O1C)
1: ON, 0: OFF
bit 2
Multi-function photocoupler output 2 (terminal
DO2-O2C)
1: ON, 0: OFF
bit 3 -
F
Reserved
000A
Pulse train output (Units: 1/1 Hz, setting range: 0 to 32000)
000B - 000E
Reserved
000F
Command selection setting
bit 0
Reserved
bit 1
Input for the PID setpoint
1: Enables target values from Modbus
bit 2
Torque Limit Input
1: Enables setting values from Modbus
bit 3
Torque Compensation Input
1: Enables setting values from Modbus
bit 4
Reserved
bit 5
PID feedback from the Modbus
1: Enables PID feedback (15FF (Hex.)) from
Modbus
bit 6 -
B
Reserved
bit C
Terminal DI5 input of broadcast message
1: Enabled, 0: Disabled
bit D
Terminal DI6 input of broadcast message
1: Enabled, 0: Disabled
bit E
Terminal DI7 input of broadcast message
1: Enabled, 0: Disabled
bit F
Reserved
0010 - 001F
Reserved
15C0
bit 0
Extended multi-function input command 1
bit 1
Extended multi-function input command 2
bit 2
Extended multi-function input command 3
bit 3 -
F
Reserved
3004
Time Setting
Setting range: 0000 to 2359 (decimal), the default value at
energize: 0000
Set the hour and the minute in HHMM format.
•
HH: 00 to 23 (decimal)
•
MM: 00 to 59 (decimal)
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...