240
SIEPCYEUOQ2V01A Q2V Technical Manual
Code
Name
Causes
Possible Solutions
CyC
MECHATROLINK
CommCycleSettingErr
The communications cycle setting of the controller
is not in the permitted range of the
MECHATROLINK interface option.
Set the communications cycle of the controller in the permitted
range of the MECHATROLINK interface option.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
CyPo
Cycle Power to Accept Changes
Although
F6-15 = 1 [Comm. Option Parameters
Reload = Reload Now]
, the drive does not update
the communication option parameters.
Re-energize the drive to update the communication option
parameters.
Code
Name
Causes
Possible Solutions
dEv
Speed Deviation
The load is too large.
Decrease the load.
The acceleration/deceleration times are too short.
Increase the values set in
C1-01 to C1-08 [Acceleration/
Deceleration Times]
.
The
dEv
detection level settings are incorrect.
Adjust
F1-10 [Speed Dev Level]
and
F1-11 [Speed Dev Delay
Time]
.
The load is locked up.
Examine the machine.
The holding brake is stopping the motor.
Release the holding brake.
Note:
•
The drive detects this error if the difference between the detected speed and the speed reference is more than the setting of
F1-10
for longer than
F1-11
.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Select = Alarm]
will activate.
•
If the drive detects this error, it will operate the motor as specified by the stopping method set in
F1-04 [Speed Dev Detection Select]
.
Code
Name
Causes
Possible Solutions
dnE
Drive Disabled
A terminal set for
H1-xx = 1A [Drive Enable]
turned OFF.
Examine the operation sequence.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Select = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
qAL2
Q2pack Alarm 2
There was an error in the Q2pack program.
Examine the Q2pack program and remove the cause of the fault.
This is not a drive fault.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Select = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
qAL3
Q2pack Alarm 3
There was an error in the Q2pack program.
Examine the Q2pack program and remove the cause of the fault.
This is not a drive fault.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Select = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
qAL1
Q2pack Alarm
There was an error in the Q2pack program.
Examine the Q2pack program and remove the cause of the fault.
This is not a drive fault.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Select = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
E5
MECHATROLINK Watchdog
Timer Err
The drive detected a watchdog circuit exception
while it received data from the controller.
Examine the MECHATROLINK cable connection. If this error
occurs frequently, examine the wiring and decrease the effects of
electrical interference as specified by these manuals:
•
MECHATROLINK-II Installation Guide (MECHATROLINK
Members Association, manual number MMATDEP011)
•
MECHATROLINK-III Installation Manual
(MECHATROLINK Members Association, publication
number MMATDEP018)
Note:
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Select = Alarm]
will activate.
•
If the drive detects this error, it will operate the motor as specified by the stopping method set in
F6-25 [MLII Watchdog Error Sel]
.
Code
Name
Causes
Possible Solutions
EF
FWD/REV Run Command Input
Error
A forward command and a reverse command were
input at the same time for longer than 0.5 s.
Examine the forward and reverse command sequence and correct
the problem.
Note:
•
If the drive detects
EF
, the motor will ramp to stop.
•
If the drive detects this error, the terminal assigned to
H2-01 to H2-03 = 4 [MFDO Function Select = Alarm]
will be ON.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...