SIEPCYEUOQ2V01A Q2V Technical Manual
241
Code
Name
Causes
Possible Solutions
EF0
Option Card External Fault
The communication option card received an
external fault from the controller.
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input from the controller.
A programming error occurred on the controller
side.
Examine the operation of the controller program.
Note:
•
The drive detects this error if the alarm function on the external device side is operating.
•
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Select = Alarm]
will activate.
•
If the drive detects this error, it will operate the motor as specified by the stopping method set in
F6-03 [Comm Ext Flt Select (EF0)]
.
Code
Name
Causes
Possible Solutions
EF1
External Fault (Terminal DI1)
MFDI terminal DI1 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI1.
External Fault [H1-01 = 2C to 2F]
is set to MFDI
terminal DI1, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Select = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
EF2
External Fault (Terminal DI2)
MFDI terminal DI2 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI2.
External Fault [H1-02 = 2C to 2F]
is set to MFDI
terminal DI2, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
EF3
External Fault (Terminal DI3)
MFDI terminal DI3 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI3.
External Fault [H1-03 = 2C to 2F]
is set to MFDI
terminal DI3, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
EF4
External Fault (Terminal DI4)
MFDI terminal DI4 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI4.
External Fault [H1-04 = 2C to 2F]
is set to MFDI
terminal DI4, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
EF5
External Fault (Terminal DI5)
MFDI terminal DI5 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI5.
External Fault [H1-05 = 2C to 2F]
is set to MFDI
terminal DI5, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm]
will activate.
Code
Name
Causes
Possible Solutions
EF6
External Fault (Terminal DI6)
MFDI terminal DI6 caused an external fault through
an external device.
1.
Find the device that caused the external fault and remove the
caus.
2.
Clear the external fault input in the MFDI.
The wiring is incorrect.
Correctly connect the signal line to MFDI terminal DI6.
External Fault [H1-06 = 2C to 2F]
is set to MFDI
terminal DI6, but the terminal is not in use.
Correctly set the MFDI.
Note:
If the drive detects this error, the terminal set to
H2-01 to H2-03 = 4 [MFDO Function Selection = Alarm]
will activate.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...