248
SIEPCYEUOQ2V01A Q2V Technical Manual
Code
Name
Causes
Possible Solutions
Settings for N.C. and N.O. input
[H1-xx]
for these
functions were selected at the same time:
•
Setting value
34 [Fast Stop NO]
•
Setting value
35 [Fast Stop NC]
Remove one of the function settings.
These settings were entered while
H1-xx = 9 [Ext
Ref 1/2]
:
•
b1-15 = 4 [Freq. Ref. Sel. 2 = Pulse Train Input]
•
H6-01 ≠ 0 [PI Pulse Train Function ≠ Freq Ref]
Set
H6-01 = 0
.
These settings were entered while
H1-xx = 9 [Ext
Ref 1/2]
:
•
b1-15 = 3 [Option PCB]
or
b1-16 = 3 [Run
Comm. Sel 2 = Option PCB]
•
No option is connected to the drive.
Connect an input option to the drive.
These settings were entered while
H1-xx = 9 [Ext
Ref 1/2]
:
•
b1-15 = 1 [Analog Input]
•
H3-02 ≠ 4 [AI1 Function Selection ≠ Freq Ref/
BIAS]
or
H3-10 ≠ 0 [AI2 Function Selection ≠
Freq Ref/BIAS]
Set
H3-02 = 0
or
H3-10 = 0
.
These parameters are set at the same time:
•
H1-xx ≠ 1A [Drive Enable]
•
H2-xx = 2 [Drive Enable]
Correct the parameter settings.
These parameters are set at the same time:
•
H6-01 ≠ 3 [PG Feedback]
•
H1-xx = 15 [FWD/REV Det]
Correct the parameter settings.
These parameters are set at the same time:
•
H1-xx = 65/66 [Up2 Command / Dw2
Command]
•
H3-01, H3-09 = 1 [AI1 Signal Level Select, AI2
Signal Level Select = 0 to +10 V (Without Lower
Limit)]
Remove one of the function settings.
Code
Name
Causes
Possible Solutions
oPE05
Run Cmd/Freq Ref Source Sel Err
The setting to assign the Run command or
frequency reference to an option card or the pulse
train input is incorrect.
Correct the parameter settings.
b1-01 = 3 [Freq. Ref. Sel. 1 = Option PCB]
is set,
but there is no option card connected to the drive.
b1-02 = 3 [Run Comm. Sel 1 = Option PCB]
is set,
but there is no option card connected to the drive.
Connect an option card to the drive.
These parameters are set at the same time:
•
b1-01 = 4 [Pulse Train Input]
•
H6-01 ≠ 0 [PI Pulse Train Function ≠ Freq Ref]
Set
H6-01 = 0
.
Code
Name
Causes
Possible Solutions
oPE07
Analog Input Selection Error
The settings for
H3-02 and H3-10 [MFAI Function
Select]
and
H7-30 [Virtual AIn Select Function]
overlap.
Set
H3-02, H3-10, and H7-30
correctly to prevent overlap.
Note:
It is possible to set these functions to multiple analog input
terminals at the same time:
•
Setting value
4 [Freq Ref/BIAS]
•
Setting values
0 [Through Mode]
These parameters are set at the same time:
•
H3-02, H3-10, H7-30 = F [PID Fbk]
•
H6-01 = 1 [PI Pulse Train Function = PIDFbk
Value]
These parameters are set at the same time:
•
H3-02, H3-10, H7-30 = 10 [PID SetPoint]
•
H6-01 = 2 [PID SP Value]
These parameters are set at the same time:
•
H3-02, H3-10, H7-30 = 10
•
b5-18 = 1 [b5-19 PID SP Selection = Enabled]
These parameters are set at the same time:
•
H6-01 = 2
•
b5-18 = 1
Remove the function settings that are not in use.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...