SIEPCYEUOQ2V01A Q2V Technical Manual
249
Code
Name
Causes
Possible Solutions
oPE08
Parameter Selection Error
A function was set that is not compatible with the
control method selected in
A1-02 [Control Method]
.
1.
Push ENTER Key to show
U1-18 [oPE Fault Parameter]
,
and find parameters that are not in the applicable setting
range.
2.
Correct the parameter settings.
Note:
If more than one error occurs at the same time, other
oPExx
errors have priority over
oPE02
.
When
A1-02 = 2 [OLVector]
, you used these
parameter settings:
•
n2-02 > n2-03 [AFR Time 1 > AFR Time 2]
•
C4-02 > C4-06 [Trq Comp Delay Time > M2
Trq Comp Delay Time]
•
Set
n2-02 < n2-03
.
•
Set
C4-02 < C4-06
.
When
A1-02 = 0 [V/f Control]
, you used these
parameter settings:
•
H6-01 = 3 [PI Pulse Train Function = PG
Feedback]
•
H1-xx = 61 [MFDI Function Select = Motor 2
Select]
Correct the parameter settings.
Note:
You cannot use Speed Feedback (V/F Control) with the Motor
Switch function.
When
A1-02 = 5 [PM OLVector]
, you set
E5-02 to
E5-07 [PM q-Axis Inductance (mH/Phase)] = 0
.
•
Set
E5-01 [PM Mot Code Selection]
correctly as specified by
the motor.
•
For specialized motors, refer to the motor test report and set
E5-xx
correctly.
When
A1-02 = 5, 6 [PM OLVector, PM
AOLVector]
, you used these parameter settings:
•
E5-09 = 0.0 [PM BackEMF Vpeak (mV/(rad/ s))
= 0.0 mV/(rad/s)]
•
E5-24 = 0.0 [PM BackEMF L-L Vrms (mV/rpm)
= 0.0 mV/min
-1
]
Set
E5-09
or
E5-24
to the correct value.
When
A1-02 = 5, 6
, you set
E5-09 ≠ 0
and
E5-24 ≠
0
.
Set
E5-09 = 0
or
E5-24 = 0
.
When
A1-02 = 6
, you set these parameters:
•
n8-57 = 0 [High-Freq Injection = Disabled]
•
You set
E1-09 [Min Output Frequency]
< the
5% value of
E1-06
.
Correct the parameter settings.
When
A1-02 = 6
, you set these parameters:
•
n8-35 = 1 [InitRotorPos Selection = Pull-In]
•
n8-57 = 1 [Enabled]
Correct the parameter settings.
When
A1-02 = 8 [EZ Vector]
, you used these
parameter settings:
•
E9-01 = 1, 2 [Motor Type Selection = PM,
SynRM]
•
b3-24 = 2 [SpSrch Method Selection = Current
Det2]
When
E9-01 = 1 or 2
,
set b3-24 = 1 [Speed Estimation]
.
Code
Name
Causes
Possible Solutions
oPE09
PID Control Selection Fault
These parameters are set at the same time:
•
b5-15 ≠ 0.0 [Sleep Start Level ≠ 0.0 Hz]
•
b1-03 = 2, 3 [Stopping Method Selection = DC
Inj->Stop, Timed Coast->Stop]
•
Set
b5-15 ≠ 0.0
.
•
Set
b1-03 = 0, 1 [Ramp->Stop, Coast->Stop]
.
These parameters are set at the same time:
•
b5-01 = 1 [Enabled]
and
b5-72 = 0, 1 [PID D-
FF Mode = D=Fdback, D=FdFwd]
•
d2-02 ≠ 0.0 [FRef Lower Limit ≠ 0.0%]
Correct the parameter settings.
These parameters are set at the same time:
•
b5-01 = 1 and b5-72 = 0, 1 [D=Fdback, D=
FdFwd]
•
b5-11 = 1 [PID Output Reverse Selection =
Negative lower limit]
Correct the parameter settings.
These parameters are set at the same time:
•
b5-01 = 1 and b5-70 = 1 [PID MainRefMode =
Fref + PID] and B5-72 = 0, 1 [D=Fdback, D=
FdFwd]
•
d2-02 ≠ 0.0
has been set.
Correct the parameter settings.
Note:
The drive detects this error if the PID control function selection is incorrect.
(When
b5-01 = 1 [PID Enable = Enabled]
)
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...