250
SIEPCYEUOQ2V01A Q2V Technical Manual
Code
Name
Causes
Possible Solutions
oPE10
V/f Data Setting Error
The parameters that set the V/f pattern do not
satisfy these conditions:
•
For motor 1:
E1-09 ≤ E1-07 < E1-06 ≤ E1-11 ≤
E1-04 [Min Output Frequency ≤ Mid A
Frequency < Base Frequency ≤ Mid B
Frequency ≤ Max Output Frequency]
•
For motor 2:
E3-09 ≤ E3-07 < E3-06 ≤ E3-11 ≤
E3-04 [M2 Min Out Frequency ≤ M2 Mid A
Frequency < M2 Base Frequency ≤ M2 Mid B
Frequency ≤ M2 Max Out Frequency]
Set the parameters correctly to satisfy the conditions.
Code
Name
Causes
Possible Solutions
oPE11
Carrier Frequency Setting Error
These parameters are set at the same time:
•
C6-05 > 6 [Carrier Freq Proportional Gain >
6]
•
C6-04 > C6-03 [Carrier Lower Frequency Limit
> Carrier Upper Frequency Limit]
Note:
When
C6-05 < 7
,
C6-04
becomes disabled. The
drive sets the carrier frequency to the value set
to
C6-03
.
C6-02 to C6-05
settings are not in the applicable
setting range.
Set
C6-02 to C6-05
correctly.
Code
Name
Causes
Possible Solutions
oPE13
Pulse Monitor Selection Error
H6-06 = 101, 102, 105, or 116 [PO Mon.Selection
= Frequency Reference, Output Frequency, Motor
Speed, Output Frequency after Soft Starter]
has not
been set when
H6-07 = 0 [PO Freq.Scaling = 0
Hz]
.
Set
H6-06
correctly.
Code
Name
Causes
Possible Solutions
oPE16
Energy Saving Constants Error
The Energy Saving parameters are not set in the
applicable setting range.
Make sure that
E5-xx
is set correctly as specified by the motor
nameplate data.
Code
Name
Causes
Possible Solutions
oPE33
Digital Output Selection Error
These two parameters are set at the same time:
•
H2-60 ≠ 0 [NO,NC,CM 2nd Function ≠ Through
Mode]
•
H2-01 = 1xx [NO,NC,CM FuncSelection =
Inverse output of xx]
These two parameters are set at the same time:
•
H2-63 ≠ 0 [DO1 2nd Function ≠ Through Mode]
•
H2-02 = 1xx [DO1-O1C Func Selection =
Inverse output of xx]
These two parameters are set at the same time:
•
H2-66 ≠ 0 [DO2 2nd Function ≠ Through Mode]
•
H2-03 = 1xx [DO2-O2C Func Selection =
Inverse output of xx]
Clear the
H2-01 to H2-03 = 1xx [Inverse output of xx]
settings.
Note:
If you use the function to output logical calculation results
(
H2-60, H2-63, H2-66 ≠ 0
), you cannot set
H2-01 to H2-03 =
1xx
.
These parameter pairs are set incorrectly:
•
H2-21 [Compare1 Low Limit]
>
H2-22
[Compare1 Up Limit]
•
H2-27 [Compare2 Low Limit]
>
H2-28
[Compare2 Up Limit]
•
Set parameters
H2-21
≤
H2-22
.
•
Set parameters
H2-27
≤
H2-28
.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...