7.10 Troubleshooting Without Fault Display
262
SIEPCYEUOQ2V01A Q2V Technical Manual
◆
The Drive Frequency Reference Is Different than the Controller Frequency
Reference Command
Causes
Possible Solutions
The analog input gain and bias for the frequency reference input are set
incorrectly.
Examine the gain and bias settings for the analog inputs that set the frequency reference.
•
Terminal AI1:
H3-03 [AI1 Gain Setting]
,
H3-04 [AI1 Bias Setting]
•
Terminal AI2:
H3-11 [AI2 Gain Setting]
,
H3-12 [AI2 Bias Setting]
The drive is receiving frequency bias signals from analog input terminals
AI1 and AI2 and the sum of all signals makes the frequency reference.
•
Examine parameters
H3-02, H3-10 [MFAI Function Select]
. If both of these parameters =
4
[Freq Ref/BIAS]
, change the settings.
•
Use
U1-13, U1-14 [Terminal AI1 InputLv, Terminal AI2 InputLv]
to make sure that the analog
input values set to terminals AI1 and AI2 are applicable.
PID control is enabled.
If PID control is not necessary, set
b5-01 = 0 [PID Enable = Disabled]
.
Note:
When PID control is enabled, the drive adjusts the output frequency as specified by the target
value. The drive will only accelerate to the maximum output frequency set in
E1-04 [Max
Output Frequency]
while PID control is active.
◆
The Motor Speed Is Not Stable When Using a PM Motor
Causes
Possible Solutions
E5-01 [PM Mot Code Selection]
is set incorrectly.
Refer to
“
Motor Performance Fine-Tuning
”
in the technical manual.
The drive is operating the motor at more than the specified speed control
range.
Examine the speed control range and adjust the speed.
The motor is hunting.
Adjust these parameters to have the largest effect:
•
n8-55 [Load Inertia]
•
n8-45 [SpdFbck Det.Gain]
•
C4-02 [Trq Comp Delay Time]
Hunting occurs at start.
Increase the value set in
C2-01 [Jerk@Start of Accel]
.
Too much current is flowing through the drive.
Set
E5-01 [PM Mot Code Selection]
correctly as specified by the motor. For special-purpose
motors, enter the correct value to
E5-xx
as specified by the motor test report.
Operation is not stable when
n8-57 = 1 [High-Freq Injection = Enabled]
.
•
Do High Frequency Injection Auto-Tuning.
•
Decrease the value set in
n8-41 [HFI PoleDet Pgain]
in increments of 0.5.
Note:
Set
n8-41 > 0.0
for IPM motors.
◆
There Is Too Much Motor Oscillation and the Rotation Is Irregular
Causes
Possible Solutions
Unsatisfactory balance of motor phases.
•
Make sure that the drive input power voltage supplies stable power.
•
Set
L8-05 = 0 [In PhaseLoss Selection = Disabled]
.
The motor is hunting.
•
Set
n1-01 = 1 [HuntPrev Selection = Enabled]
.
•
Increase the value of
n2-01 [AFR Gain]
or
n2-02 [AFR Time 1]
.
◆
Deceleration Takes Longer Than Expected When Dynamic Braking Is Enabled
Causes
Possible Solutions
The stall prevention during deceleration setting is incorrect.
•
Examine the setting for
L3-04 [StallP@Decel Enable]
.
•
When the drive has a dynamic braking option installed, set
L3-04 = 0 [Disabled]
.
•
If the drive detects
ov [Overvoltage]
, set
L3-04 = 1 [Enabled] and L3-50 = 2 [StallP@Decel
Mode = Gen Purpose w/ DB Resistor]
.
The deceleration time setting is too long.
Set
C1-02, C1-04, C1-06, or C1-08 [Deceleration Times]
to applicable values.
The motor torque is not sufficient.
Use a larger motor.
Note:
If these items are correct, the demand on the motor is more than the motor capacity:
•
Parameter settings are correct.
•
The drive does not detect
ov [Overvoltage]
.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...