SIEPCYEUOQ2V01A Q2V Technical Manual
273
◆
Alarm Outputs for Maintenance Monitors
You can use
H2-xx [MFDO Function Select]
to send a message that tells you when a specified component is near
the end of its performance life estimate. Set the applicable value to
H2-xx
as shown in
for your
component.
When the specified component is near the end of its performance life estimate, the MFDO terminals set for
H2-xx
= 63 [Maintenance]
will activate, and the keypad will show an alarm that identifies the component to replace.
Table 8.9 Maintenance Period Alarms
Display
Alarm Name
Cause
Possible Solutions
Digital Outputs
(Setting Value in
H2-xx)
LT-1
Cooling Fan
Maintenance Time
The cooling fan is at 90% of its expected
performance life.
Replace the cooling fan, then set
o4-03 = 0 [Fan.Oper
Setting = 0 h]
to reset the cooling fan operation time.
63
LT-2
Capacitor
Maintenance Time
The capacitors for the main circuit and
control circuit are at 90% of expected
performance life.
Replace the board or the drive.
Contact the manufacturer or your nearest sales
representative to replace the board.
LT-3
SoftChargeBypassRe
lay MainteTime
The soft charge bypass relay is at 90% of its
performance life estimate.
Replace the board or the drive.
Contact the manufacturer or your nearest sales
representative to replace the board.
LT-4
IGBT Maintenance
Time (50%)
The IGBT is at 50% of its expected
performance life.
Check the load, carrier frequency, and output frequency.
TrPC
IGBT Maintenance
Time (90%)
The IGBT is at 90% of its expected
performance life.
Replace the IGBT or the drive.
4
◆
Related Parameters
Replace the component, then set Maintenance Setting
o4-03, o4-05, o4-07, and o4-09 = 0
to reset the
Maintenance Monitor. If these parameters are not reset after the corresponding parts have been replaced, the
Maintenance Monitor function will continue to count down the performance life from the value that was reached
with the old part. If the Maintenance Monitor is not reset, the drive will not have the correct value of the
performance life for the new component.
Note:
The maintenance period changes for different operating environments.
Table 8.10 Maintenance Setting Parameters
No.
Name
Function
o4-03
Fan.Oper Setting
Sets the value from which to start the cumulative drive cooling fan operation time in 10-hour units.
Note:
When
o4-03 = 30
has been set, the drive will count the operation time for the cooling fan from 300 hours
and
U4-03 [Fan Oper.Time]
will show
300 h
.
o4-05
Cap.Maint.Setting
Sets the value from which to start the count for the main circuit capacitor maintenance period as a percentage.
o4-07
PreChgRly Preset Maintenance Cnt
Sets as a percentage the value from which to start the count for the soft charge bypass relay maintenance
time.
o4-09
IGBT Preset Maintenance Cnt
Sets the value from which to start the count for the IGBT maintenance period as a percentage.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...