302
SIEPCYEUOQ2V01A Q2V Technical Manual
■
Single-Phase 200 V Class
Table 10.14 Carrier Frequency and Rated Current Derating (Single-Phase 200 V)
Model
Rated Current (A)
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
B001
0.8
0.8
0.8
0.8
0.7
0.6
1.2
1.1
1.0
0.9
0.8
0.6
B002
1.6
1.6
1.6
1.6
1.4
1.3
1.9
1.9
1.7
1.6
1.4
1.3
B004
3.0
3.0
3.0
3.0
2.7
2.4
3.5
3.5
3.2
3.0
2.7
2.4
B006
5.0
5.0
5.0
5.0
4.5
4.0
6.0
6.0
5.4
5.0
4.5
4.0
B010
8.0
8.0
8.0
7.5
7.0
6.4
9.6
9.1
8.3
7.7
7.1
6.4
B012
11.0
11.0
11.0
10.4
9.6
8.8
12.2
11.9
11.0
10.4
9.6
8.8
B018
17.6
17.6
17.6
16.6
15.3
14.1
21.0
19.8
18.1
17.0
15.5
14.1
Table 10.15 AOLV/PM Carrier Frequency and Rated Current Derating (Single-Phase 200 V)
Model
Rated Current (A)
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
2 kHz
4 kHz
6 kHz
8 kHz
10 kHz
12 kHz
B001
0.8
0.8
0.8
0.7
0.6
0.5
1.2
1.1
0.9
0.8
0.6
0.5
B002
1.6
1.6
1.6
1.5
1.3
1.1
1.9
1.9
1.7
1.5
1.3
1.1
B004
3.0
3.0
3.0
2.8
2.4
2.0
3.5
3.5
3.1
2.8
2.4
2.0
B006
5.0
5.0
5.0
4.6
4.0
3.4
6.0
5.8
5.2
4.6
4.0
3.4
B010
8.0
8.0
7.8
7.1
6.4
5.7
9.6
8.8
8.0
7.2
6.4
5.6
B012
11.0
11.0
10.7
9.7
8.8
7.9
12.2
11.6
10.7
9.7
8.8
7.9
B018
17.6
17.6
17.1
15.6
14.1
12.6
21.0
19.3
17.5
15.8
14.1
12.3
■
Three-Phase 400 V Class
Table 10.16 Carrier Frequency and Rated Current Derating (Three-Phase 400 V)
Model
Rated Current (A)
Heavy Duty Rating (HD)
[C6-01 = 0]
Normal Duty Rating (ND)
[C6-01 = 1]
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
2 kHz
5 kHz
8 kHz
10 kHz
12.5 kHz
15 kHz
4001
1.2
1.2
1.2
1.1
0.9
0.7
1.2
1.2
1.2
1.1
0.9
0.7
4002
1.8
1.8
1.8
1.6
1.3
1.1
2.1
2.1
1.8
1.6
1.3
1.1
4004
3.4
3.4
3.4
3.0
2.5
2.0
4.1
4.0
3.4
3.0
2.5
2.0
4005
4.8
4.8
4.8
4.3
3.6
2.9
5.4
5.4
4.8
4.2
3.6
2.9
4007
5.5
5.5
5.5
4.9
4.1
3.3
7.1
6.5
5.5
4.9
4.1
3.3
4009
7.3
7.3
7.3
6.5
5.4
4.4
8.9
8.6
7.3
6.5
5.4
4.4
4012
9.2
9.2
9.2
8.1
6.8
5.5
11.9
10.8
9.2
8.2
6.8
5.5
4018
14.8
14.8
14.8
13.1
11.0
8.9
17.8
17.3
14.7
13.1
11.0
8.8
4023
18.0
18.0
18.0
13.1
11.0
11
23.4
21.3
18.2
16.1
13.4
11
4031
24.0
24.0
24.0
21.3
17.8
14
31.0
28.2
24.1
21.3
17.9
14
4038
31.0
31.0
31.0
27.5
23.0
19
38.0
36.3
31.0
27.5
23.0
19
4044
39.0
39.0
39.0
34.5
29.0
23
44.0
44.0
39.0
34.5
29.0
23
4060
45.0
45.0
45.0
39.9
33.4
27
60.0
54.5
46.3
40.8
33.9
27
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...