SIEPCYEUOQ2V01A Q2V Technical Manual
325
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
b5-90
(0B90)
EZsleep Unit
Sets the measurement units for
b5-91 [EZsleep Min Spd]
and
b5-92 [EZsleep Level]
.
0 : rpm
1 : 0.1Hz units
0
(0, 1)
b5-91
(0B91)
RUN
EZsleep Min Spd
Sets the minimum speed for the EZ Sleep/Wakeup function. This parameter uses the
largest value from
b5-91
,
b5-34 [PID Out Low Limit Level]
, and
d2-02 [FRef Lower
Limit]
.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
b5-92
(0B92)
RUN
EZsleep Level
Sets the value that the output frequency or motor speed must be less than for longer than
b5-93 [EZsleep Time]
to enter Sleep Mode.
0.0 Hz or 0 min
-1
(r/min)
(0.0 to 590.0 Hz or 0 to
35400 min
-1
(r/min))
b5-93
(0B93)
RUN
EZsleep Time
Sets the length of time that the output frequency or motor speed must be less than
b5-92
[EZsleep Level]
to enter Sleep Mode.
5.0 s
(0.0 - 1000.0 s)
b5-94
(0B94)
RUN
EZsleep Wake Level
Sets the level at which the drive resumes operation when exiting Sleep Mode.
0.00%
(0.00 - 600.00%)
b5-95
(0B95)
EZsleep Wake Mode
Sets the wake-up mode to use when exiting Sleep Mode.
0 : Setpoint Delta
1 : Absolute
0
(0, 1)
b5-96
(0B96)
RUN
EZsleep Wake Time
Sets the EZ Wake-up time.
1.0 s
(0.0 - 1000.0 s)
◆
b6: DWELL FUNCTION
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
b6-01
(01B6)
Dwell Ref.@Start
Sets the output frequency that the drive will hold momentarily when the motor starts.
0.0
(Determined by A1-02)
b6-02
(01B7)
Dwell Time@Start
Sets the length of time that the drive will hold the output frequency when the motor
starts.
0.0 s
(0.0 - 10.0 s)
b6-03
(01B8)
Dwell Ref@Stop
Sets the output frequency that the drive will hold momentarily when ramping to stop the
motor.
0.0
(Determined by A1-02)
b6-04
(01B9)
Dwell Time@Stop
Sets the length of time for the drive to hold the output frequency when ramping to stop
the motor.
0.0 s
(0.0 - 10.0 s)
◆
b8: ENERGY SAVING
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
b8-01
(01CC)
eSave Ctrl Selection
Sets the Energy-saving control function.
0 : Disabled
1 : Enabled
2 : Search Enabled
Note:
When
A1-02 = 6 [Control Method = PM AOLVector]
, you can only select setting
2
in Expert Mode.
0
(0 - 2)
b8-02
(01CD)
RUN
Expert
eSave Ctrl Gain
Sets the gain for Energy-saving control.
Determined by A1-02
(0.0 - 10.0)
b8-03
(01CE)
RUN
Expert
eSave Filter Time
Sets the responsiveness for Energy-saving control.
Determined by A1-02
,
C6-01 and o2-04
(0.00 - 10.00 s)
b8-04
(01CF)
Expert
eSave Coef. Value
Sets the Energy-saving control coefficient to maintain maximum motor efficiency. The
default setting is for Yaskawa motors.
Determined by C6-01,
E2-11, and o2-04
(0.00 - 655.00)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...