340
SIEPCYEUOQ2V01A Q2V Technical Manual
11.8
F: OPTIONS
◆
F1: ENCODER
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
F1-02
(0381)
PGOpen Detection
Select
Sets the method to stop the motor or let the motor continue operating when the drive
detects
PGo [Encoder (PG) Feedback Loss]
.
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
3 : Alarm Only
4 : No Alarm Display
Note:
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train
Function = PG Feedback]
to enable this parameter.
1
(0 - 4)
F1-03
(0382)
Overspeed Detection
Selection
Sets the method to stop the motor or let the motor continue to operate when the drive
detects
oS [Overspeed]
.
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
3 : Alarm Only
Note:
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train
Function = PG Feedback]
to enable this parameter.
1
(0 - 3)
F1-04
(0383)
Speed Dev Detection
Select
Sets the method to stop the motor or let the motor continue to operate when the drive
detects
dEv [Speed Deviation]
.
0 : Ramp->Stop
1 : Coast->Stop
2 : Fast Stop (C1-09)
3 : Alarm Only
Note:
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train
Function = PG Feedback]
to enable this parameter.
3
(0 - 3)
F1-08
(0387)
Overspeed Level
Sets the detection level of
oS [Overspeed]
as a percentage when the maximum output
frequency is 100%.
Note:
•
Parameter
A1-02 [Control Method]
selects which parameter is the maximum
output frequency.
–
A1-02 ≠ 8 [EZ Vector]
:
E1-04 [Max Output Frequency]
–
A1-02 = 8
:
E9-02 [Maximum Speed]
•
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train
Function = PG Feedback]
to enable this parameter.
115%
(0 - 120%)
F1-09
(0388)
Overspeed Delay Time
Sets the length of time that the speed feedback must be more than the
F1-08
level to
cause
oS [Overspeed]
.
Note:
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train
Function = PG Feedback]
to enable this parameter.
Determined by A1-02
(0.0 - 2.0 s)
F1-10
(0389)
Speed Dev Level
Sets the detection level of
dEv [Speed Deviation]
as a percentage when the maximum
output frequency is 100%.
Note:
•
Parameter
A1-02 [Control Method]
selects which parameter is the maximum
output frequency.
–
A1-02 ≠ 8 [EZ Vector]
:
E1-04 [Max Output Frequency]
–
A1-02 = 8
:
E9-02 [Maximum Speed]
•
When
A1-02 = 0 [Control Method = V/f Control]
, set
H6-01 = 3 [PI Pulse Train
Function = PG Feedback]
to enable this parameter.
10%
(0 - 50%)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...