368
SIEPCYEUOQ2V01A Q2V Technical Manual
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L3-06
(0494)
StallP Level@Run
Sets the output current level at which the Stall Prevention function is enabled during run
when the drive rated output current is 100%.
Note:
This parameter is applicable when
L3-05 = 1 [StallP@RUN Enable = Enabled]
and
L3-51 = 0, 1 [StallP@RUNDecTime = Dec Time 1 (C1-02), Dec Time 2 (C1-04)]
.
Determined by C6-01
and L8-38
(5 - 150%)
L3-11
(04C7)
Overvolt Supression
Select
Sets the overvoltage suppression function.
0 : Disabled
1 : Enabled
0
(0, 1)
L3-17
(0462)
DCBus Regul.Level
Sets the target value for the DC bus voltage when the overvoltage suppression function
and the Decel Stall Prevention function (Intelligent Stall Prevention) are active.
200 V Class: 375 V, 400
V: 750 V
(200 V Class: 150 to 400
V, 400 V Class: 300 to
800 V)
L3-20
(0465)
Expert
DCBus VoltAdj Gain
Sets the proportional gain used to control the DC bus voltage.
Determined by A1-02
(0.00 - 5.00)
L3-21
(0466)
Expert
OVSup Acc/Dec Gain
Sets the proportional gain to calculate acceleration and deceleration rates.
Determined by A1-02
(0.10 - 10.00)
L3-22
(04F9)
StallP@Acc
Deceleration Time
Sets the momentary deceleration time that the drive will use when it tries to accelerate a
PM motor and detected motor stalls. This function is applicable when
L3-01 = 2 [StallP
Mode@Accel = General Purpose]
.
0.0 s
(0.0 - 6000.0 s)
L3-23
(04FD)
CHP Stall P Selection
Sets the function to automatically decrease the Stall Prevention Level during Run for
constant output ranges.
1 : Level@L3-06
2 : Automatic Reduction
1
(1, 2)
L3-24
(046E)
Expert
Acc@Rated Torque
Sets the motor acceleration time to reach the maximum frequency at the motor rated
torque for stopped single-drive motors.
Determined by o2-04,
C6-01, E2-11, and E5-01
(0.001 - 10.000 s)
L3-25
(046F)
Expert
Load Inertia Ratio
Sets the ratio between motor inertia and machine inertia.
1.0
(0.1 - 1000.0)
L3-26
(0455)
Expert
DC Bus Capacitors
Extension
Sets the capacity for external main circuit capacitors. Usually it is not necessary to
change this setting. Sets this parameter when you use the KEB Ride-Thru function.
0 μF
(0 to 65000 μF)
L3-27
(0456)
StallP Detect Time
Sets a delay time between reaching the Stall Prevention level and starting the Stall
Prevention function.
60 ms
(0 - 5000 ms)
L3-34
(016F)
Expert
Torque Lim.Delay Time
Sets the filter time constant that returns the torque limit to its initial value when KEB
operation operates in Single Drive KEB Ride-Thru mode.
Determined by A1-02
(0.000 - 1.000 s)
L3-35
(0747)
Expert
SpAgree Width@StallP
Sets the width for speed agreement when
L3-04 = 1 [StallP@Decel Enable = Enabled]
and
L3-50 = 1 [StallP@Decel Mode = Automatic Decel Reduction]
. Usually it is not
necessary to change this setting.
0.00 Hz
(0.00 - 1.00 Hz)
L3-36
(11D0)
VibSup Gain@Accel
Sets the gain to suppress current and motor speed hunting during operation when
L3-01
= 4 [StallP Mode@Accel = ILim Mode]
. Usually it is not necessary to change this
setting.
Determined by A1-02
(0.0 - 100.0)
L3-37
(11D1)
Expert
CurLim ITime@Accel
Suppresses current hunting during acceleration. Usually it is not necessary to change
this setting.
5 ms
(0 - 100 ms)
L3-38
(11D2)
Expert
CurLim PGain@Accel
Suppresses current hunting and overshooting that occurs when the drive stalls during
acceleration. Usually it is not necessary to change this setting.
10.0
(0.0 - 100.0)
L3-39
(11D3)
CurLim Filt@Accel
Sets the time constant to adjust the acceleration rate when
L3-01 = 4 [StallP
Mode@Accel = ILim Mode]
. Usually it is not necessary to change this setting.
100.0 ms
(1.0 - 1000.0 ms)
L3-40
(11D4)
CurLim SCurve@Acc/
Dec
Sets the function to enable and disable the best S-curve characteristic used for current-
limited acceleration.
0 : Disabled
1 : Enabled
0
(0, 1)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...