SIEPCYEUOQ2V01A Q2V Technical Manual
373
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L8-10
(04B6)
Fan Operate Selection
Sets operation of the heatsink cooling fan.
1 : Dur Run (OffDly)
2 : Always On
3 : Fan ON @Heating of Drive
1
(1 - 3)
L8-11
(04B7)
Fan Off-Delay Time
Sets the length of time that the drive will wait before it stops the cooling fan after it
cancels the Run command when
L8-10 = 1 [Fan Operate Selection = Dur Run
(OffDly)]
.
60 s
(0 - 300 s)
L8-12
(04B8)
Ambient Temperature
Setting
Sets the ambient temperature of the drive installation area.
Note:
The setting range changes when the
L8-35 [Installation Selection]
value changes:
•
0 [IP00/IP20/Open-Chassis]
: -10 °C to +60 °C
•
1 [Side-by-Side Mounting]
: -10 °C to +50 °C
•
2 [UL Type 1]
: -10 °C to +50 °C
•
3 [Ext. Heatsink]
: -10 °C to +50 °C
40 °C
(-10 °C - +60 °C)
L8-15
(04BB)
oL2@LoSpeed Selection
Sets the function to decrease drive overload at low speeds to prevent damage to the
main circuit transistor during low speed operation (at 6 Hz or slower) to prevent
oL2
[Drive Overloaded]
.
Note:
Contact the manufacturer or your nearest sales representative before disabling this
function at low speeds. If you frequently operate drives with high output current in
low speed ranges, it can cause heat stress and decrease the life span of drive IGBTs.
0 : Disabled
1 : Enabled
1
(0, 1)
L8-18
(04BE)
Soft CurrLim Selection
Set the software current limit selection function to prevent damage to the main circuit
transistor caused by too much current.
0 : Disabled
1 : Enabled
1
(0, 1)
L8-19
(04BF)
Frq Reduct@oHPre-
Alarm
Sets the ratio at which the drive derates the frequency reference during an
oH
alarm.
0.8
(0.1 - 0.9)
L8-27
(04DD)
OverCurr Det Gain
Sets the PM motor overcurrent detection level as a percentage of the motor rated current
value.
Note:
Parameter
A1-02 [Control Method]
selects which parameter is the motor rated
current.
•
A1-02 ≠ 8 [EZ Vector]
:
E5-03 [PM Mot Rated Current (FLA)]
•
A1-02 = 8
:
E9-06 [Motor Rated Current]
300.0%
(0.0 - 1000.0%)
L8-29
(04DF)
LF2 Unbalance Selection
Sets the function to detect
LF2
.
0 : Disabled
1 : Enabled
1
(0, 1)
L8-31
(04E1)
LF2 Detect Time
Sets the LF2 [Output Current Imbalance] detection time.
3
(1
–
100)
L8-35
(04EC)
Installation Selection
Sets the type of drive installation.
0 : IP00/IP20/Open-Chassis
1 : Side-by-Side Mounting
2 : UL Type 1
3 : Ext. Heatsink
0
(0 - 3)
L8-40
(04F1)
Carrier Red Off-Delay
Time
Sets the length of time until the automatically reduced carrier frequency returns to the
condition before the reduction.
Determined by A1-02
(0.00 - 2.00 s)
L8-41
(04F2)
HCA alarm Selection
Sets the function to cause an
HCA [Current Alarm]
when the output current is more
than 150% of the drive rated current.
0 : Disabled
1 : Enabled
0
(0, 1)
L8-51
(0471)
Expert
STPo Current Level
Sets the
STPo [Motor Step-Out Detected]
detection level as a percentage of the motor
rated current.
Note:
Parameter
A1-02 [Control Method]
selects which parameter is the motor rated
current.
•
A1-02 = 5 [PM OLVector]
:
E5-03 [PM Mot Rated Current (FLA)]
•
A1-02 = 8 [EZ Vector]
:
E9-06 [Motor Rated Current]
0.0%
(0.0 - 300.0%)
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...