SIEPCYEUOQ2V01A Q2V Technical Manual
395
No.
(Hex.)
Name
Description
MFAO Signal Level
U2-12
(008B)
OutStat@PrevFault
Shows the status of the MFDO terminals at the most recent fault where
= ON and
= OFF.
For example,
U2-12
shows
when terminals NO and DO2 are ON.
Use
U1-11 [Out Terminal Status]
to monitor the actual MFDO terminal status.
bit0 : Terminal NO/NC-CM
bit1 : Terminal DO1-O1C
bit2 : Terminal DO2-O2C
bit3 : Not used (normal value of [ ]).
bit4 : Not used (normal value of [ ]).
bit5 : Not used (normal value of [ ]).
bit6 : Not used (normal value of [ ]).
bit7 : Not used (normal value of [ ]).
No signal output available
U2-13
(008C)
DrvStat@PrevFault
Shows the status of the MFDO terminals at the most recent fault where
= ON and
= OFF.
For example,
U2-13
shows
during run.
Use
U1-12 [Drive Status]
to monitor the actual MFDO terminal status.
bit0 : During Run
bit1 : During zero-speed
bit2 : During reverse
bit3 : During fault reset signal input
bit4 : During speed agreement
bit5 : Drive Ready
bit6 : During minor fault detection
bit7 : During fault detection
No signal output available
U2-14
(008D)
OpeTime@PreFault
Shows the cumulative operation time of the drive at the fault that occurred most recently.
Use
U4-01 [Cumulative OpeTime]
to monitor the actual cumulative operation time.
Unit: 1 h
No signal output available
U2-15
(07E0)
SFSFreq@PrevFault
Shows the output frequency after soft start at the fault that occurred most recently.
Use
U1-16 [SFS Output Frequency]
to monitor the actual output frequency after soft start.
Unit: 0.01 Hz
No signal output available
U2-16
(07E1)
qCurrent@PrevFault
Shows the q-axis current of the motor at the fault that occurred most recently.
Use
U6-01 [Iq Sec Current]
to monitor the actual q-Axis current of the motor.
Unit: 0.1 %
No signal output available
U2-17
(07E2)
dCurrent@PreFault
Shows the d-axis current of the motor at the fault that occurred most recently.
Use
U6-02 [Id ExcCurrent]
to monitor the actual d-Axis current of the motor.
Unit: 0.1 %
No signal output available
U2-19
(07E4)
RotorDev@PrevFault
Shows the amount of control axis deviation (Δθ) at the fault that occurred most recently.
Use
U6-10 [ContAxisDeviation]
to monitor the actual amount of control axis deviation (Δθ).
Unit: 0.1 °
No signal output available
U2-20
(008E)
DrvTemp@PreFault
Shows the heatsink temperature at the fault that occurred most recently.
Use
U4-08 [Heatsink Temperature]
to monitor the actual temperature of the heatsink.
Unit: 1 °C
No signal output available
U2-21
(1166)
Expert
STPoSt@PrevFault
Monitors conditions to detect
STPo [Motor Step-Out Detected]
faults. The bit for each condition
is shown as
= ON or
= OFF.
For example,
U2-21
shows
when the drive detects excessive current.
bit0 : Excessive current
bit1 : Induced voltage deviation
bit2 : d-axis current deviation
bit3 : Motor lock at startup
bit4 : Acceleration stall continue
bit5 : Acceleration stall repeat
bit6 : Not used (normal value of [ ]).
bit7 : Not used (normal value of [ ]).
No signal output available
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...