SIEPCYEUOQ2V01A Q2V Technical Manual
397
No.
(Hex.)
Name
Description
MFAO Signal Level
U4-06
(07D6)
SoftChgRelay Maint
Shows the operation time of the soft charge bypass relay as a percentage of the replacement life of
the soft charge bypass relay.
Use parameter
o4-07 [PreChgRly Preset Maintenance Cnt]
to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
10 V: 100%
U4-07
(07D7)
IGBT Maintenance
Shows the operation time of the IGBTs as a percentage of the replacement life of the IGBTs.
Set parameter
o4-09 [IGBT Preset Maintenance Cnt]
to reset this monitor.
Unit: 1%
Note:
Replace the drive when this monitor is 90%.
10 V: 100%
U4-08
(0068)
Heatsink Temperature
Shows the heatsink temperature of the drive.
Unit: 1 °C
10 V: 100 °C
U4-09
(005E)
LED Check
Turns on all of the keypad LEDs to make sure that the LEDs operate correctly.
1.
With
U4-09
displayed, press
.
All LEDs on the keypad will turn on.
Note:
When Safety input 2 CH is open (STo), READY will flash.
No signal output available
U4-10
(005C)
kWh Lower 4Digits
Displays the lower 4 digits of the watt hour value for the drive.
Unit: 1 kWh
Note:
The watt hour is displayed in 9 digits. Monitor
U4-11 [kWh Upper 5Digits]
shows the upper 5
digits and
U4-10
shows the lower 4 digits.
Example for 12345678.9 kWh:
U4-10
: 678.9 kWh
U4-11
: 12345 MWh
No signal output available
U4-11
(005D)
kWh Upper 5Digits
Shows the upper 5 digits of the watt hour value for the drive.
Unit: 1 MWh
Note:
Monitor
U4-11
shows the upper 5 digits and
U4-10 [kWh Lower 4Digits]
shows the lower 4
digits.
Example for 12345678.9 kWh:
U4-10
: 678.9 kWh
U4-11
: 12345 MWh
No signal output available
U4-13
(07CF)
Peak Hold Current
Shows the hold value of the peak value (rms) for the drive output current.
Use
U4-14 [PeakHold OutFreq]
to show the drive output frequency at the time that the drive
holds the output current.
The drive will hold the peak hold current at the next start up and restart of the power supply. The
drive keeps the value that was under hold during baseblock (during stop).
The keypad shows the value of
U4-13
in amperes (A). When looking at the monitor through
Modbus communications, the current is
“
8192 = drive rated current (A)
”
. Calculate the current
from the monitor value that is in at Modbus communications using
“
Numerals being displayed /
8192 × drive rated current (A).
Unit: When the drive model changes, the display units for this parameter also change.
•
0.01 A units: 2001 to 2042, B001 to B018, 4001 to 4023
•
0.1A units: 2056 to 2082, 4031 to 4060
No signal output available
U4-14
(07D0)
PeakHold OutFreq
Displays the output frequency at which the peak value (rms) of the drive output current is held.
The peak hold current can be monitored by
U4-13 [Peak Hold Current]
.
The peak hold output frequency will be cleared at the next startup and restart of the power supply.
The drive keeps the value that was under hold during baseblock (during stop).
Unit: 0.01 Hz
No signal output available
U4-16
(07D8)
MotorOLEstimate (oL1)
Shows the integrated value of
oL1 [Motor Overload]
as a percentage of
oL1
detection level.
Unit: 0.1%
10 V: 100%
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...