11.17 Parameters that Change from the Default Settings with A1-02 [Control Method]
SIEPCYEUOQ2V01A Q2V Technical Manual
403
11.17 Parameters that Change from the Default Settings with
A1-02 [Control Method]
The values for the parameters in these tables depend on the values for parameter
A1-02
. When you change the
setting for
A1-02
, the default settings will change.
Table 11.1 A1-02 = 0, 2 [V/f Control, OLVector]
No.
Name
Range
Unit
Control Method (A1-02 Setting)
V/f
(0)
OLV
(2)
b2-01
ZSpd/DCI Threshold
0.0 - 10.0
0.1 Hz
0.5
0.5
b2-04
DCInj Time@Stop
0.00 - 10.00
0.01 s
0.50
0.50
b3-01
SpSrch@Start Selection
0 - 1
1
0
0
b3-02
SpSrch Deactivation
Current
0 - 200
1%
120
100
b3-08
Speed ACR PGain for
Estimation
0.00 - 6.00
0.01
b3-09
Speed ACR ITime for
Estimation
0.0 - 1000.0
0.1 ms
2.0
2.0
b3-14
Speed Bi-Directional
Search
0 - 1
1
0
0
b5-15
Sleep Start Level
0.0 - 400.0
0.1 Hz
0.0
0.0
b6-01
Dwell Ref.@Start
0.0 - 400.0
0.1 Hz
0.0
0.0
b6-03
Dwell Ref@Stop
0.0 - 400.0
0.1 Hz
0.0
0.0
b8-02
eSave Ctrl Gain
0.0 - 10.0
0.1
-
0.7
b8-03
eSave Filter Time
0.00 - 10.00
0.01 s
-
0.50
b8-19
eSave Search Frequency
10 - 300
1 Hz
100
100
C1-11
Ac/Dec Switch Frequency
0.0 - 400.0
0.1 Hz
0.0
0.0
C2-01
Jerk@Start of Accel
0.00 - 10.00
0.01 s
0.20
0.20
C3-01
Slip Comp Gain
0.0 - 2.5
0.1
0.0
1.0
C3-02
Slip Comp Delay Time
0 - 10000
1 ms
2000
200
C4-01
Trq Comp Gain
0.00 - 2.50
0.01
1.00
1.00
C4-02
Trq Comp Delay Time
0 - 10000
1 ms
200
20
C5-01
ASR PGain 1
0.00 - 300.00
0.01
-
-
C5-02
ASR ITime 1
0.000 - 60.000
0.001 s
-
-
C5-03
ASR PGain 2
0.00 - 300.00
0.01
-
-
C5-04
AASR ITime 2
0.000 - 10.000
0.001 s
-
-
C5-06
ASR Delay Time
0.000 - 0.500
0.001 s
-
-
C5-07
ASR Gain Switch
Frequency
0.0 - 400.0
0.1 Hz
0.0Hz
0.0Hz
C6-02
Carrier Frequency
Selection
1 - F
1
1
d3-01
Jump Frequency 1
0.0 - 400.0
0.1 Hz
0.0
0.0
d3-02
Jump Frequency 2
0.0 - 400.0
0.1 Hz
0.0
0.0
d3-03
Jump Frequency 3
0.0 - 400.0
0.1 Hz
0.0
0.0
d3-04
Jump Frequency Width
0.0 - 20.0
0.1 Hz
1.0
1.0
E1-04
Max Output Frequency
40.0 - 400.0
0.1 Hz
60.0
E1-05
Max Output Voltage
0.0 - 255.0
0.1 V
200.0
200.0
E1-06
Base Frequency
0.0 - 400.0
0.1 Hz
60.0
E1-07
Mid A Frequency
0.0 - 400.0
0.1 Hz
3.0
E1-08
Mid A Voltage
0.0 - 255.0
0.1 V
11.0
E1-09
Min Output Frequency
0.0 - 400.0
0.1 Hz
0.5
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...