11.17 Parameters that Change from the Default Settings with A1-02 [Control Method]
404
SIEPCYEUOQ2V01A Q2V Technical Manual
No.
Name
Range
Unit
Control Method (A1-02 Setting)
V/f
(0)
OLV
(2)
E1-10
Min Output Voltage
0.0 - 255.0
0.1 V
2.0
F1-09
Overspeed Delay Time
0.0 - 2.0
0.1 s
-
-
L1-01
Motor Cool Type for OL1
Calc
0 - 4
1
1
1
L2-31
KEB StartV Offset Level
0 - 100
1 V
0
0
L3-05
StallP@RUN Enable
0 - 3
1
1
1
L3-20
DCBus VoltAdj Gain
0.00 - 5.00
0.01
1.00
0.30
L3-21
OVSup Acc/Dec Gain
0.10 - 10.00
0.01
1.00
1.00
L3-36
VibSup Gain@Accel
0.0 - 100.0
0.1
10.0
20.0
L4-01
SpAgree Det.Level
0.0 - 400.0
0.1
0.0 Hz
0.0 Hz
L4-02
SpAgree Det.Width
0.0 - 20.0
0.1
2.0 Hz
2.0 Hz
L4-03
SpAgree Det.Level(+/-)
-400.0 - +400.0
0.1
0.0 Hz
0.0 Hz
L4-04
SpAgree Det.Width(+/-)
0.0 - 20.0
0.1
2.0 Hz
2.0 Hz
L8-40
Carrier Red Off-Delay
Time
0.00 - 2.00
0.01 s
0.50
0.50
L8-90
STPo Detect Level
0 - 5000
1
-
-
n5-04
Speed Response Frequency
0.00 - 500.00
0.00 Hz
-
-
n8-35
InitRotorPos Selection
0 - 2
1
-
-
n8-51
Ac/Dec Pull-In Current
0 - 200%
1
0
0
o1-03
FrqDisplay Unit Selection
0 - 3
1
0
0
o1-04
V/f Pattern Unit for
Display
0 - 1
1
-
-
*1
The default setting changes when the setting for
o2-04 [Drive KVA Selection]
changes.
*2
The default setting changes when the setting of
C6-01 [ND/HD Duty Selection]
changes.
*3
The setting range changes when the setting of
E5-01 [PM Mot Code Selection]
changes when
A1-02 = 5 [PM OLVector]
.
*4
The default setting changes when the drive model and
E1-03 [V/f Pattern Selection]
change.
*5
This is the value for 200 V class drives. Double the value for 400 V class drives.
*6
When
A1-02 = 5 [PM OLVector]
, the maximum value of the setting range is 100.0.
*7
When
A1-02 = 5 [PM OLVector]
, the setting range is -100.0 to +100.0.
Table 11.2 A1-02 = 5, 6, 8 [PM OLVector, PM AOLVector, EZ Vector]
No.
Name
Range
Unit
Control Method (A1-02 Setting)
OLV/PM
(5)
AOLV/PM
(6)
EZOLV
(8)
b2-01
ZSpd/DCI Threshold
0.0 - 10.0
0.1
0.5 Hz
1.0%
0.5Hz
b2-04
DCInj Time@Stop
0.00 - 10.00
0.01 s
0.00
0.00
0.00
b3-01
SpSrch@Start Selection
0 - 1
1
0
0
0
b3-02
SpSrch Deactivation
Current
0 - 200
1%
-
-
-
b3-08
Speed ACR PGain for
Estimation
0.00 - 6.00
0.01
0.30
0.30
0.30
b3-09
Speed ACR ITime for
Estimation
0.0 - 1000.0
0.1 ms
4.0
4.0
4.0
b3-14
Speed Bi-Directional
Search
0 - 1
1
-
-
0
b5-15
Sleep Start Level
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
b6-01
Dwell Ref.@Start
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
b6-03
Dwell Ref@Stop
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
b8-02
eSave Ctrl Gain
0.0 - 10.0
0.1
-
-
-
b8-03
eSave Filter Time
0.00 - 10.00
0.01 s
-
-
-
b8-19
eSave Search Frequency
10 - 300
1 Hz
100
100
20
C1-11
Ac/Dec Switch Frequency
0.0 - 400.0
0.1
0.0 Hz
0.0%
0.0%
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...