11.20 Defaults by Drive Model and Duty Rating ND/HD
414
SIEPCYEUOQ2V01A Q2V Technical Manual
Name
Unit
Default
-
Drive Model
-
B001
B002
B004
B006
C6-01
ND/HD Duty
Selection
-
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive KVA
Selection
Hex.
30
31
32
33
E2-11
(E4-11, E5-
02)
Motor Rated
Power (kW)
kW
0.1
0.2
0.2
0.4
0.4
0.75
0.75
1.1
b3-08
Speed ACR
PGain for
Estimation
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-26
Dir. Determ.
Level
-
1000
1000
1000
1000
1000
1000
1000
1000
b8-03
eSave Filter
Time
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
eSave Coef.
Value
-
481.7
356.9
356.9
288.2
288.2
223.7
223.7
196.6
C6-02
Carrier
Frequency
Selection
-
4
7
4
7
4
7
4
7
E2-01
(E4-01)
Mot Rated
Current (FLA)
A
0.6
1.1
1.1
1.9
1.9
3.3
3.3
6.2
E2-02
(E4-02)
Mot Rated
Slip
Hz
2.5
2.6
2.6
2.9
2.9
2.5
2.5
2.6
E2-03
(E4-03)
Mot No-Load
Current
A
0.4
0.8
0.8
1.2
1.2
1.8
1.8
2.8
E2-05
(E4-05)
Motor L-L
Resistance
Ω
35.98
20.56
20.56
9.842
9.842
5.156
5.156
1.997
E2-06
(E4-06)
Motor Leak
Inductance
%
21.6
20.1
20.1
18.2
18.2
13.8
13.8
18.5
E2-10
(E4-10)
Motor Iron
Loss
W
6
11
11
14
14
26
26
53
E5-01
PM Mot Code
Selection
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
RideThrough
Time@Power
Loss
s
0.1
0.1
0.1
0.1
0.1
0.1
0.2
0.2
L2-03
Min Baseblck
Time
s
0.2
0.3
0.2
0.3
0.2
0.3
0.3
0.4
L2-04
Powloss
Ramp
Time@recov
ery
s
0.3
0.3
0.3
0.3
0.3
0.3
0.3
0.3
L2-05
UV Detection
Lvl (Uv1)
-
160
160
160
160
160
160
160
160
L3-02
StallP
Level@Accel
%
150
120
150
120
150
120
150
120
L3-06
StallP
Level@Run
%
150
120
150
120
150
120
150
120
L3-24
Acc@Rated
Torque
s
0.178
0.178
0.178
0.178
0.178
0.142
0.142
0.142
L8-02
Overheat Alm
Level
°C
105
105
105
105
115
115
115
115
L8-09
Ground Fault
Selection
-
0
0
0
0
0
0
0
0
n1-03
HuntPrev
Time Constant
ms
10
10
10
10
10
10
10
10
n3-02
HSB CurrLim
Level
%
150
120
150
120
150
120
150
120
n5-02
Mot Inertia
Acceleration
Time
s
0.178
0.178
0.178
0.142
0.178
0.142
0.142
0.142
*1
Parameters within parentheses are for motor 2.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...