11.20 Defaults by Drive Model and Duty Rating ND/HD
SIEPCYEUOQ2V01A Q2V Technical Manual
415
No.
Name
Unit
Default
-
Drive Model
-
B010
B012
B018
C6-01
ND/HD Duty
Selection
-
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
o2-04
Drive KVA
Selection
Hex.
34
35
37
E2-11
(E4-11, E5-02)
Motor Rated
Power (kW)
kW
1.5
2.2
2.2
3.0
3.7
5.5
b3-04
SpSrch V/F Gain
%
100
100
100
100
100
100
b3-06
Speed Curr Lev1
for Estimation
-
0.5
0.5
0.5
0.5
0.5
0.5
b3-08
Speed ACR
PGain for
Estimation
-
0.5
0.5
0.5
0.5
0.5
0.5
b3-26
Dir. Determ.
Level
-
1000
1000
1000
1000
1000
1000
b8-03
eSave Filter Time
s
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
eSave Coef.
Value
-
169.4
156.8
156.8
136.4
122.9
94.75
C6-02
Carrier Frequency
Selection
-
3
7
3
7
3
7
E2-01
(E4-01)
Mot Rated
Current (FLA)
A
6.2
8.5
8.5
11.4
14
19.6
E2-02
(E4-02)
Mot Rated Slip
Hz
2.6
2.9
2.9
2.7
2.73
1.5
E2-03
(E4-03)
Mot No-Load
Current
A
2.8
3
3
3.7
4.5
5.1
E2-05
(E4-05)
Motor L-L
Resistance
Ω
1.997
1.601
1.601
1.034
0.771
0.399
E2-06
(E4-06)
Motor Leak
Inductance
%
18.5
18.4
18.4
19
19.6
18.2
E2-10
(E4-10)
Motor Iron Loss
W
53
77
77
91
112
172
E5-01
PM Mot Code
Selection
-
FFFF
FFFF
FFFF
FFFF
FFFF
FFFF
L2-02
RideThrough
Time@Power
Loss
s
0.3
0.3
0.5
0.5
1
1
L2-03
Min Baseblck
Time
s
0.4
0.5
0.5
0.5
0.6
0.7
L2-04
Powloss Ramp
Time@recovery
s
0.3
0.3
0.3
0.3
0.3
0.3
L2-05
UV Detection Lvl
(Uv1)
-
160
160
160
160
160
160
L3-02
StallP
Level@Accel
%
150
120
150
120
150
120
L3-06
StallP
Level@Run
%
150
120
150
120
150
120
L3-24
Acc@Rated
Torque
s
0.166
0.145
0.145
0.145
0.154
0.168
L8-02
Overheat Alm
Level
°C
105
105
110
110
115
115
L8-09
Ground Fault
Selection
-
0
0
0
0
0
0
n1-03
HuntPrev Time
Constant
ms
10
10
10
10
10
10
n3-02
HSB CurrLim
Level
%
150
120
150
120
150
120
n5-02
Mot Inertia
Acceleration
Time
s
0.166
0.145
0.145
0.145
0.154
0.168
*1
Parameters within parentheses are for motor 2.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...