11.20 Defaults by Drive Model and Duty Rating ND/HD
418
SIEPCYEUOQ2V01A Q2V Technical Manual
Name
Unit
Default
-
Drive Model
-
4007
4009
4012
4018
C6-01
ND/HD Duty
Selection
-
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive KVA
Selection
Hex.
95
96
97
99
E2-11
(E4-11, E5-
02)
Motor Rated
Power (kW)
kW
2.2
3.0
3.0
3.7
4.0
5.5
5.5
7.5
L2-05
UV Detection
Lvl (Uv1)
-
380
380
380
380
380
380
380
380
L3-02
StallP
Level@Accel
%
150
120
150
120
150
120
150
120
L3-06
StallP
Level@Run
%
150
120
150
120
150
120
150
120
L3-24
Acc@Rated
Torque
s
0.145
0.145
0.145
0.154
0.154
0.168
0.168
0.175
L8-02
Overheat Alm
Level
°C
90
90
115
115
110
110
120
120
L8-09
Ground Fault
Selection
-
0
0
0
0
0
0
0
0
n1-03
HuntPrev
Time Constant
ms
10
10
10
10
10
10
10
10
n3-02
HSB CurrLim
Level
%
150
120
150
120
150
120
150
120
n5-02
Mot Inertia
Acceleration
Time
s
0.145
0.145
0.145
0.154
0.154
0.168
0.168
0.175
*1
Parameters within parentheses are for motor 2.
Name
Unit
Default
-
Drive Model
-
4023
4031
4038
4044
C6-01
ND/HD Duty
Selection
-
HD
ND
HD
ND
HD
ND
HD
ND
0
1
0
1
0
1
0
1
o2-04
Drive KVA
Selection
Hex.
9A
9C
9D
9E
E2-11
(E4-11, E5-
02)
Motor Rated
Power (kW)
kW
7.5
11
11
15
15
18.5
18.5
22
b3-04
SpSrch V/F
Gain
%
100
100
100
100
100
100
100
100
b3-06
Speed Curr
Lev1 for
Estimation
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-08
Speed ACR
PGain for
Estimation
-
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b3-26
Dir. Determ.
Level
-
1000
1000
1000
1000
1000
1000
1000
1000
b8-03
eSave Filter
Time
s
0.5
0.5
0.5
0.5
0.5
0.5
0.5
0.5
b8-04
eSave Coef.
Value
-
145.38
140.88
140.88
126.26
126.26
115.74
115.74
103.58
C6-02
Carrier
Frequency
Selection
-
3
7
3
7
3
7
3
7
E2-01
(E4-01)
Mot Rated
Current (FLA)
A
13.3
19.9
19.9
26.5
26.5
32.9
32.9
38.6
E2-02
(E4-02)
Mot Rated
Slip
Hz
1.3
1.7
1.7
1.6
1.6
1.67
1.67
1.7
E2-03
(E4-03)
Mot No-Load
Current
A
4
5.6
5.6
7.6
7.6
7.8
7.8
9.2
E2-05
(E4-05)
Motor L-L
Resistance
Ω
1.152
0.922
0.922
0.55
0.55
0.403
0.403
0.316
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...