11.21 Parameters Changed by PM Motor Code Selection
SIEPCYEUOQ2V01A Q2V Technical Manual
423
No.
Name
Unit
Motor Code (setting value of E5-01)
E1-09
Min Output Frequency
Hz
18.0
18.0
18.0
L3-24
Acc@Rated Torque
s
0.100
0.100
0.100
n5-02
Mot Inertia Acceleration Time
s
0.100
0.100
0.100
n8-49
Heavy Load Id Current
%
0.0
0.0
0.0
◆
Yaskawa SSR1 Series IPM Motors (Derated Torque)
Table 11.9 SSR1 Series Motor Code Setting for Specification of 200 V at 1750 min
-1
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-01
PM Mot Code Selection
-
1202
1203
1205
1206
1208
120A
Voltage Class
V
200
200
200
200
200
200
Capacity
kW
0.4
0.75
1.5
2.2
3.7
5.5
Motor Rotation Speed
min
-1
1750
1750
1750
1750
1750
1750
E5-02
PM Mot Rated Power (kW)
kW
0.4
0.75
1.5
2.2
3.7
5.5
E5-03
PM Mot Rated Current (FLA)
A
1.77
3.13
5.73
8.44
13.96
20.63
E5-04
PM Mot Pole Count
-
6
6
6
6
6
6
E5-05
PM Mot Resistance (Ohms/
Phase)
Ω
8.233
2.284
1.470
0.827
0.455
0.246
E5-06
PM d-Axis Inductance (mH/
Phase)
mH
54.84
23.02
17.22
8.61
7.20
4.86
E5-07
PM q-Axis Inductance (mH/
Phase)
mH
64.10
29.89
20.41
13.50
10.02
7.43
E5-09
PM BackEMF Vpeak (mV/
(rad/ s))
mVs/rad
223.7
220.3
240.8
238.0
238.7
239.6
E5-24
PM BackEMF L-L Vrms
(mV/rpm)
mV/min
-1
0.0
0.0
0.0
0.0
0.0
0.0
E1-04
Max Output Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
E1-05
Max Output Voltage
V
190.0
190.0
190.0
190.0
190.0
190.0
E1-06
Base Frequency
Hz
87.5
87.5
87.5
87.5
87.5
87.5
E1-09
Min Output Frequency
Hz
4.4
4.4
4.4
4.4
4.4
4.4
L3-24
Acc@Rated Torque
s
0.092
0.076
0.051
0.066
0.075
0.083
n5-02
Mot Inertia Acceleration
Time
s
0.092
0.076
0.051
0.066
0.075
0.083
n8-49
Heavy Load Id Current
%
-7.6
-11.5
-9.1
-19.0
-18.7
-23.4
*1
The default setting changes when the setting for
o2-04 [Drive KVA Selection]
changes.
Table 11.10 SSR1 Series Motor Code Setting for Specification of 200 V at 1750 min
-1
(r/min)
No.
Name
Unit
Motor Code (setting value of E5-01)
E5-01
PM Mot Code Selection
-
120B
120D
120E
120F
1210
Voltage Class
V
200
200
200
200
200
Capacity
kW
7.5
11
15
18.5
22
Motor Rotation Speed
min
-1
1750
1750
1750
1750
1750
E5-02
PM Mot Rated Power (kW)
kW
7.5
11.0
15.00
18.50
22.00
E5-03
PM Mot Rated Current (FLA)
A
28.13
41.4
55.4
68.2
80.6
E5-04
PM Mot Pole Count
-
6
6
6
6
6
E5-05
PM Mot Resistance (Ohms/
Phase)
Ω
0.198
0.094
0.066
0.051
0.037
E5-06
PM d-Axis Inductance (mH/
Phase)
mH
4.15
3.40
2.45
2.18
1.71
E5-07
PM q-Axis Inductance (mH/
Phase)
mH
5.91
3.91
3.11
2.55
2.05
E5-09
PM BackEMF Vpeak (mV/(rad/
s))
mVs/rad
258.2
239.3
248.1
253.6
250.0
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...