434
SIEPCYEUOQ2V01A Q2V Technical Manual
■
A1-03: Init Parameters
No.
(Hex.)
Name
Description
Default
(Range)
A1-03
(0103)
Init Parameters
Sets parameters to default values.
0
(0 - 3330)
Note:
•
After you initialize the drive, the drive automatically sets
A1-03 = 0
.
•
User Parameters can save the parameter values for your application and use these values as default values for drive initialization.
•
To use the 2 motor switchover function, first turn OFF the terminal to which
H1-xx = 61 [MFDI Function Select = A1-03: Motor 2
Select]
is set, then change the
A1-03
setting. An incorrect procedure will trigger
oPE08 [Parameter Selection Error]
.
0 : No Initialization
1110 : User / Solution Initialization
Sets parameters to the values set by the user as user settings. Set
o2-03 = 1 [UserPar Set Default Values = Set
defaults]
to save the user settings.
You can save the parameter settings that were adjusted for the test run as user-set default values to the drive.
When you make changes to the parameter values after you save the settings as User Parameter Settings, the drive
will set the parameters to the User Parameter Setting value when you initialize with
A1-03 = 1110
.
Follow this procedure to save User Parameter setting values, and to do a User Initialization.
1. Set parameters correctly for the application.
2. Set
o2-03 = 1 [UserPar Set Default Values = Set defaults]
.
This saves parameter settings for a User Initialization.
The drive will then automatically set
o2-03 = 0
.
3. Set
A1-03 = 1110
to reset to the saved parameter settings.
When you initialize the drive, the drive sets the parameter values to the User Parameter setting values.
2220 : 2-Wire Initialization
Sets MFDI terminal DI1 to Forward Run and terminal DI2 to Reverse Run, and resets all parameters to default
settings.
3330 : 3-Wire Initialization
Sets MFDI terminal DI1 to Run, terminal DI2 to Stop, and terminal DI5 to FWD/REV, and resets all parameters to
default settings.
The drive will not initialize the parameters in
when
A1-03 = 2220, 3330
.
Table 12.2 Parameters that are not Initialized Using a 2-Wire Sequence or a 3-Wire Sequence
No.
Name
A1-00
Language Selection
A1-02
Control Method
A1-07
Q2pack Enable
E1-03
V/f Pattern Selection
E5-01
PM Mot Code Selection
E5-02
PM Mot Rated Power (kW)
E5-03
PM Mot Rated Current (FLA)
E5-04
PM Mot Pole Count
E5-05
PM Mot Resistance (Ohms/Phase)
E5-06
PM d-Axis Inductance (mH/Phase)
E5-07
PM q-Axis Inductance (mH/Phase)
No.
Name
E5-09
PM BackEMF Vpeak (mV/(rad/ s))
E5-24
PM BackEMF L-L Vrms (mV/rpm)
E5-25
Polar Est Timeout
F6-08
Comm Par RST@Initialize
F6-xx/F7-xx
Communication Option Parameters
Set
F6-08 = 1 [Comm Par RST@Initialize = Factory
Default - Reset]
to initialize communication option
parameters.
L8-35
Installation Selection
o2-04
Drive KVA Selection
q1-xx - q8-xx
q1-01 to q8-40: Q2pack Parameters
r1-xx
r1: Q2PACK JOINTS
Note:
•
When
A1-03 = 2220, 3330
, the drive automatically set
A1-05 [Password Setting] = 0000
. Make sure that you set the password again
for applications where a password is necessary.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...