3.2 Standard Connection Diagram
44
SIEPCYEUOQ2V01A Q2V Technical Manual
*3
When you use a regenerative converter or regenerative unit, set
L8-55 = 0 [DB IGBT Protection = Disable]
. If
L8-55 = 1 [Enabled]
,
the drive will detect
rF [Braking Resistor Fault]
.
*4
When you use a regenerative converter, regenerative unit, braking resistor, or braking resistor unit, set
L3-04 = 0 [StallP@Decel
Enable = Disabled]
. If
L3-04 = 1 [Enabled]
, the drive could possibly not stop in the specified deceleration time.
*5
When you use an ERF-type braking resistor, set
L8-01 = 1 [3%ERF DBR Protection = Enabled]
and set a wiring sequence to de-
energize the drive with the MFDO.
*6
Cooling fan wiring is not necessary for self-cooling motors.
*7
Connect peripheral options to terminals -, +1, +2, B1, and B2.
WARNING!
Fire Hazard. Only connect factory-recommended devices or circuits to drive terminals B1, B2, -, +1, +2, and
+3 terminals. Do not connect AC power to these terminals. Incorrect wiring can cause damage to the drive and serious
injury or death from fire.
*8
Connect a 24 V power supply to terminals D24V-A0V to operate the control circuit while the main circuit power supply is OFF.
*9
To set the MFDI power supply (Sinking/Sourcing Mode or internal/external power supply), install wire jumpers between terminals
DIC-D24V and DIC-D0V.
NOTICE:
Do not close the circuit between terminals D24V and D0V. A closed circuit between these terminals will cause
damage to the drive.
•
Sinking Mode: Install a jumper between terminals DIC and D24V.
NOTICE:
Do not close the circuit between terminals DIC and D0V. A closed circuit between these terminals will cause
damage to the drive.
•
Sourcing Mode: Install a jumper between terminals DIC and D0V.
NOTICE:
Do not close the circuit between terminals DIC and D24V. A closed circuit between these terminals will cause
damage to the drive.
•
External Power Supply: No jumper is necessary between terminals DIC-D0V and terminals DIC-D24V.
*10
The maximum output current capacity for terminal RS485+ on the control circuit is 20 mA.
NOTICE:
Damage to Equipment. Do not install a jumper between ter10V and AC. A closed circuit between these
terminals will cause damage to the drive.
*11
DIP switch S1 sets terminal AI2 for voltage or current input. The default setting for S1 is current input (
“
I
”
side).
*12
Do not ground the control circuit terminals A0V or connect them to the drive.
NOTICE:
Do not ground the AC control circuit terminals and only connect the A0V terminals according to the product
instructions. If you connect the A0V terminals incorrectly, it can cause damage to the drive.
*13
Connect the positive lead from an external 24 Vdc power supply to terminal D24V and the negative lead to terminal A0V.
NOTICE:
Connect terminals D24V and A0V correctly for the 24 V power supply. If you connect the wires to the incorrect
terminals, it will cause damage to the drive.
*14
Set DIP switch S2 to
“
ON
”
to enable the termination resistor in the last drive in a Modbus network.
*15
Use only Sourcing Mode for Safe Disable input.
*16
Use multi-function analog monitor outputs with analog frequency meters, ammeters, voltmeters, and wattmeters. Do not use monitor
outputs with feedback-type signal devices.
*17
Jumper S5 sets terminal AO for voltage or current output. The default setting for S5 is voltage output (
“
V
”
side).
*18
Disconnect the wire jumpers between H1 and HC and H2 and HC to use the Safe Disable input.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...