440
SIEPCYEUOQ2V01A Q2V Technical Manual
■
Adjustments Relating to Control
When there is oscillation, rollback, or other control problems, adjust the parameters as specified by the control
method.
shows only the frequently adjusted parameters.
Note:
Torque and speed response for high-resistance and high-slip motors are slow. Adjust the torque and speed response to increase them.
Low impedance (low-slip) motors will hunt and oscillate. Adjust the torque and speed response to increase them.
■
V/f Control
When you use V/f Control, do not use
C3-01 [Slip Comp Gain]
.
Table 12.4 Adjustment of Drive Control (V/f Control)
Adjustment Description
Parameter Number
Possible Solutions
Default
Recommen
ded Setting
Prevent hunting and oscillation at
middle-range speeds (10 Hz to 40
Hz)
n1-02 [HuntPrev Gain Setting]
•
If the torque is not sufficient with heavy loads, decrease the
setting.
•
If there is hunting or oscillation with light loads, increase the
setting. Set
n1-01 = 1 [HuntPrev Selection = Enabled]
.
1.00
0.50 - 2.00
•
Increasing motor excitation
sound
•
Hunting and oscillation
suppression at low speeds and
middle-range speeds
C6-02 [Carrier Frequency
Selection]
•
If there is a loud motor excitation sound, increase the setting value.
•
If there is hunting or oscillation at low speeds or middle-range
speeds, decrease the setting value.
1 - F
•
Increase torque at low speeds
(10 Hz or lower)
•
Prevent hunting and
oscillation
C4-01 [Trq Comp Gain]
•
If the torque is not sufficient at low speeds, increase the setting
value.
•
If there is hunting or oscillation with light loads, decrease the
setting value.
1.00
0.50 - 1.50
•
Increase torque at low speeds
•
Prevent shock during start up
E1-08 [Mid A Voltage]
•
If the torque is not sufficient at low speeds, increase the setting
value.
•
If there is a large shock during start up, decrease the setting value.
15.0 V
13.0 V to 16.0
V
E1-10 [Min Output Voltage]
9.0 V
7.0 V to 10.0 V
*1
The default setting changes when the settings for
C6-01 [ND/HD Duty Selection]
and
o2-04 [Drive KVA Selection]
change.
*2
The default setting changes when the settings for
A1-02 [Control Method]
and
E1-03 [V/f Pattern Selection]
change.
*3
This is the setting for 200 V class drives. Multiply the voltage by 2 for 400 V class drives.
■
Open Loop Vector Control Method
Do not adjust parameter
C4-01 [Trq Comp Gain]
. Keep this parameter at its default setting.
If you cannot get speed accuracy during regeneration, set
C3-04 = 1 [Slip Comp@Regen = Enable>6 Hz]
. If you
cannot get speed accuracy at high speeds, set
C3-05 = 1 [Vout Limit Selection = Enabled]
.
Table 12.5 Adjustment of Drive Control (Open Loop Vector Control Method)
Adjustment description
Parameter Number
Possible Solutions
Default
Recommen
ded Setting
•
Torque, increase speed
response
•
Prevent hunting and
oscillation at middle-range
speeds (10 Hz to 40 Hz)
n2-01 [AFR Gain]
•
If torque and speed response are slow, decrease the setting value.
•
If there is hunting or oscillation, increase the setting value.
1.00
0.50 - 2.00
•
Torque, increase speed
response
•
Prevent hunting and
oscillation
C4-02 [Trq Comp Delay Time]
•
If torque and speed response are slow, decrease the setting value.
•
If there is hunting or oscillation, increase the setting value.
20 ms
20 ms to 100
ms
•
Increase speed response
•
Increase speed stability
C3-02 [Slip Comp Delay Time]
•
When speed response is slow, decrease the setting value.
•
If speed is not stable, increase the setting value.
200 ms
100 ms to 500
ms
•
Improve speed accuracy
C3-01 [Slip Comp Gain]
•
If speed is too slow, increase the setting value.
•
If speed is too fast, decrease the setting value.
1.0
0.5 - 1.5
•
Increasing motor excitation
sound
•
Prevent hunting and
oscillation at low-range speeds
(10 Hz to or lower)
C6-02 [Carrier Frequency
Selection]
•
If there is a loud motor excitation sound, increase the setting value.
•
If there is hunting or oscillation at low speeds, decrease the setting
value.
1 - F
•
Increase torque and speed
response at low speeds
•
Prevent shock during start up
E1-08 [Mid A Voltage]
•
If the torque and speed response are slow, increase the setting
value.
•
If there is a large shock during start up, decrease the setting value.
11.0 V
12.0 V to 13.0
V
E1-10 [Min Output Voltage]
2.0 V
2.0 V to 3.0 V
*1
If the value for
C4-02 [Trq Comp Delay Time]
is high, the current can increase during start up. Adjust and check the current during
start up.
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...