452
SIEPCYEUOQ2V01A Q2V Technical Manual
Note:
You can also use this diagram to wire terminal AI2.
•
Current Input
Refer to
to use a current signal input to one of the MFAI terminals.
Table 12.9 Frequency Reference Current Input
Terminal
Signal Level
Parameter Settings
Note
Signal Level
Selection
Function Selection
Gain
Bias
AI2
4 - 20 mA
H3-09 = 2
H3-10 = 4
[Freq Ref/BIAS]
H3-11
H3-12
Set DIP switch S1 to
“
I
”
for current input.
0 - 20 mA
H3-09 = 3
Figure 12.18 Example of Setting the Frequency Reference with a Current Signal to Terminal AI2
Changing between Master and Auxiliary Frequency References
Use the multi-step speed reference function to change the frequency reference input between terminals AI1 and
AI2.
2 : Modbus
Use Modbus communications to enter the frequency reference.
3 : Option PCB
Use a communications option card connected to the drive to enter the Run command.
Refer to the instruction manual included with the option card to install and set the option card.
Note:
If you set
b1-15 = 3
but you do not connect an option card,
oPE03 [Multi-Function Input Setting Err]
will flash on the keypad.
4 : Pulse Train Input
Use a pulse train signal from the pulse train input terminal PI to enter the frequency reference.
Do this procedure to make sure that the pulse train signal is operating correctly.
1. Set
b1-15 = 4
,
H6-01 = 0 [PI Pulse Train Function = Freq Ref]
.
2. Set
H6-02 [PI Frequency Scale]
to the number of pulses that determine 100% of the frequency reference.
3. The terminal set in
H1-xx = 9 [MFDI Function Select = Ext Ref 1/2]
is activated.
4. Enter a pulse train signal on the terminal PI and make sure that the keypad shows a correct frequency
reference.
■
b1-16: Run Comm. Sel 2
No.
(Hex.)
Name
Description
Default
(Range)
b1-16
(01C5)
Run Comm. Sel 2
Sets the input method for Run Command 2 when the user switches the control circuit terminals
ON/OFF to change the Run command source.
0
(0 - 3)
Activate
H1-xx = 2 [MFDI Function Select = External Reference 1/2 Selection]
to enable this parameter.
0 : Keypad
Use the keypad to enter the Run command.
You can use the JOG operation or the FWD/REV commands from the keypad.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...