464
SIEPCYEUOQ2V01A Q2V Technical Manual
■
b3-33: SpSrch@Uv Selection
No.
(Hex.)
Name
Description
Default
(Range)
b3-33
(0B3F)
Expert
SpSrch@Uv Selection
Sets the function that starts Speed Search at start-up if the drive detects a
Uv [Undervoltage]
when it receives a Run command.
1
(0, 1)
Set these three parameters as shown to enable
b3-33
:
•
L2-01 = 1, 2 [RideThru@PwrLoss = Enabled]
•
L2-50 = 0, 1 [RidThruMode@PwrLoss = Timer Controlled, While CPU Active]
•
b3-01 = 1 [SpSrch@Start Selection = Enabled]
•
b1-03 = 1 [Stopping Method Selection = Coast->Stop]
0 : Disabled
1 : Enabled
■
b3-54: Search Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-54
(3123)
Search Time
Sets the length of time that the drive will run Speed Search.
400 ms
(10 - 2000 ms)
If you set this parameter too low, Speed Search will not operate correctly.
If the drive detects
oC [Overcurrent]
immediately after Speed Search Starts:
•
Increase the value of
L2-03 [Min Baseblck Time]
and decrease the motor speed you use to start Speed Search.
•
Increases the setting value of
b3-08 [Speed ACR PGain for Estimation]
.
•
Increase the value of
b3-54
.
If the drive detects
oC
or
ov [DC Bus Overvoltage]
during Speed Search, increase the value of
b3-08
.
■
b3-55: Speed Curr Rise Time
No.
(Hex.)
Name
Description
Default
(Range)
b3-55
(3124)
Expert
Speed Curr Rise Time
Sets the length of time that the drive will increase the current from zero current to the setting
value of
b3-06 [Speed Curr Lev1 for Estimation]
.
10 ms
(10 - 2000 ms)
Gradually increase the setting value when a large quantity of current flows after speed search starts. If you set this
value too high, speed search will not operate correctly.
■
b3-56: InverseRotationSearch WaitTime
No.
(Hex.)
Name
Description
Default
(Range)
b3-56
(3126)
InverseRotationSearch
WaitTime
Sets the wait time until the drive starts inverse rotation search after it completes forward search
when you do inverse rotation search during Current Detection Speed Search.
Determined by o2-04
(0.1 - 5.0 s)
■
b3-61: Magn Pole Find Gain
No.
(Hex.)
Name
Description
Default
(Range)
b3-61
(1B96)
Expert
Magn Pole Find Gain
Sets the responsiveness for initial motor magnetic pole calculation when
A1-02 = 6 [Control
Method = PM AOLVector]
. Set
b3-61 > 0.0
for an ordinary IPM motor.
5.0
(-20.0 - +20.0)
Used when
n8-35 = 2 [InitRotorPos Selection = HiFreq Injection]
. Sets the responsiveness for initial motor
magnetic pole calculation. Set this parameter to a positive value for an ordinary monitor. When you use High
Frequency injection Tuning, it will automatically set this parameter.
◆
b4: TIMER
The drive uses timers to delay activating and deactivating MFDO terminals.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...