474
SIEPCYEUOQ2V01A Q2V Technical Manual
■
b5-10: PID Output Gain Setting
No.
(Hex.)
Name
Description
Default
(Range)
b5-10
(01AE)
RUN
PID Output Gain Setting
Sets the amount of gain to apply to the PID output.
1.00
(0.00 - 25.00)
Applies a gain to the PID output and can help when
b5-01 = 1 [PID Enable = Enabled]
and
b5-72 = 0 [PID D-
FF Mode = D=Fdback]
.
■
b5-11: PID Output Reverse Selection
No.
(Hex.)
Name
Description
Default
(Range)
b5-11
(01AF)
PID Output Reverse
Selection
Sets the function that enables and disables reverse motor rotation for negative PID control output.
0
(0, 1)
This parameter is disabled when
b5-01 = 1 [PID Enable = Enabled]
and
b5-72 = 0 [PID D-FF Mode = D=
Fdback]
. There is no limit for PID output (PID output can be positive or negative).
0 : 0 lower limit
When PID output is negative, PID output is limited to 0 and drive output is shut off.
1 : Negative lower limit
When the PID output is negative, the motor will rotate in reverse. When
b1-04 = 1 [Reverse Operation Selection
= Disabled]
, the lower limit is 0.
■
b5-12: Fdback Loss Select Mode
No.
(Hex.)
Name
Description
Default
(Range)
b5-12
(01B0)
Fdback Loss Select Mode
Sets the drive response to PID feedback loss/excess. Sets drive operation after the drive detects
PID feedback loss/excess.
0
(0 - 5)
0 : DO Only Always
The MFDO terminal set for
PID Feedback Low
or
PID Feedback High [H2-01 to H2-03 = 3E, 3F]
activates.
When the drive detects feedback loss/excess, the keypad will not show an alarm and the drive will continue
operation.
When the feedback signal is less than the level set in
b5-13 [Fdback Loss Lvl]
for longer than the time set in
b5-
14 [Fdback Loss Time]
, the MFDO terminal set for
PID Feedback Low
activates.
When the feedback signal is more than the level set in
b5-36 [PID HiHi Limit Level]
for longer than the time set
in
b5-37 [PID HiHi Time]
the MFDO terminal set for
PID Feedback High
activates.
When the feedback value is not in the detection range, the drive resets the MFDO.
1 : AL+DO Always
The drive detects
FbL [PID Feedback Loss]
and
FbH [Excessive PID Feedback]
. The MFDO terminal set for
PID Feedback Low
or
PID Feedback High [H2-01 to H2-03 = 3E, 3F]
activates. The output terminal set for
Alarm [H2-01 to H2-03 = 4]
activates and the drive continues operation.
When the feedback signal is less than the level set in
b5-13
for longer than the time set in
b5-14
, the MFDO
terminal set for
PID Feedback Low
activates.
When the feedback signal is more than the level set in
b5-36
for longer than the time set in
b5-37
, the MFDO
terminal set for
PID Feedback High
activates.
When the feedback value is not in the detection range, the drive resets the MFDO.
2 : FLT+DO Always
The drive detects
FbL
and
FbH
. MFDO terminal NO-CM turns ON, NC-CM turns OFF, and the motor coasts to
stop.
When the feedback signal is less than the level set in
b5-13
for the time set in
b5-14
, the drive detects
FbL
.
When the feedback signal is more than the level set in
b5-36
for the time set in
b5-37
, the drive detects
FbH
.
3 : DO Only@PID Enable
The MFDO terminal set for
PID Feedback Low
or
PID Feedback High
activates. The keypad will not show an
alarm. The drive continues operation.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...