SIEPCYEUOQ2V01A Q2V Technical Manual
477
■
b5-35: PID In Hi Limit Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-35
(01A0)
RUN
PID In Hi Limit Level
Sets the output upper limit for the PID control as a percentage of the Maximum Output
Frequency.
1000.0%
(0.0 - 1000.0%)
A large input value for PID control makes a high output. The drive applies this limit to the negative and positive
domains.
■
b5-36: PID HiHi Limit Level
No.
(Hex.)
Name
Description
Default
(Range)
b5-36
(01A1)
PID HiHi Limit Level
Sets the level that triggers
Excessive PID Feedback [FbH]
as a percentage of the Maximum
Output Frequency.
100%
(0 - 100%)
When the feedback signal increases to more than the level set in
b5-36
for the time set in
b5-37 [PID HiHi Time]
,
the drive will detect
Excessive PID Feedback [FbH]
.
■
b5-37: PID HiHi Time
No.
(Hex.)
Name
Description
Default
(Range)
b5-37
(01A2)
PID HiHi Time
Sets the length of time that the PID feedback signal must be more than the level set in
b5-36 [PID
HiHi Limit Level]
to cause
Excessive PID Feedback [FbH]
.
1.0 s
(0.0 - 25.5 s)
■
b5-38: PID SP User Scale for Display
No.
(Hex.)
Name
Description
Default
(Range)
b5-38
(01FE)
PID SP User Scale for
Display
Sets the value that the drive sets or shows as the PID setpoint when at the maximum output
frequency.
Determined by b5-20
(1 - 60000)
The drive uses this parameter and
b5-39 [PID SP User digits for Display]
together.
When
b5-20 = 3 [PID Unit Selection = User Units]
, the drive applies user-set PID setpoint and display units to
these parameters and monitors:
•
b5-19 [PID Setpoint Value]
•
b5-58 [PID Setpoint 2]
•
b5-59 [PID Setpoint 3]
•
b5-60 [PID Setpoint 4]
•
U5-01 [PID Feedback]
•
U5-04 [PID Setpoint]
•
U5-99 [PID Setpoint Command]
■
b5-39: PID SP User digits for Display
No.
(Hex.)
Name
Description
Default
(Range)
b5-39
(01FF)
PID SP User digits for
Display
Sets the number of digits to set and show the PID setpoint.
Determined by b5-20
(0 - 3)
The drive uses this parameter and
b5-38 [PID SP User Scale for Display]
together.
When
b5-20 = 3 [PID Unit Selection = User Units]
, the drive applies user-set PID setpoint and display units to
these parameters and monitors:
•
b5-19 [PID Setpoint Value]
•
b5-58 [PID Setpoint 2]
•
b5-59 [PID Setpoint 3]
•
b5-60 [PID Setpoint 4]
•
U5-01 [PID Feedback]
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...