478
SIEPCYEUOQ2V01A Q2V Technical Manual
•
U5-04 [PID Setpoint]
•
U5-99 [PID Setpoint Command]
0 : No Decimal Places
1 : 1 Decimal Place
2 : 2 decimal places
3 : 3 Decimal Places
■
b5-40: Fref Mon@PID
No.
(Hex.)
Name
Description
Default
(Range)
b5-40
(017F)
Fref Mon@PID
Sets the contents for monitor
U1-01 [Frequency Reference]
in PID control.
0
(0, 1)
0 : U1-01 with PID Output
Monitor
U1-01
shows the frequency reference that was increased or decreased by the PID output.
1 : U1-01 without PID Output
Monitor
U1-01
shows the actual frequency reference.
■
b5-47: PID Out Rev Operation Mode
No.
(Hex.)
Name
Description
Default
(Range)
b5-47
(017D)
PID Out Rev Operation
Mode
Sets reverse motor rotation when the PID control output is negative.
1
(0, 1)
This parameter is enabled when
b5-01 = 1 [PID Enable = Enabled]
.
0 : Lower Limit is Zero
When PID output is negative, PID output is limited to 0 and drive output is shut off.
1 : Negative Output Accepted
When the PID output is negative, the motor will rotate in reverse.
■
b5-53: PID I Ramp Limit
No.
(Hex.)
Name
Description
Default
(Range)
b5-53
(0B8F)
RUN
PID I Ramp Limit
Sets the responsiveness of PID control when the PID feedback changes quickly.
0.0 Hz
(0.0 - 10.0 Hz)
Note:
•
This parameter is disabled when set to 0.0 Hz.
•
When
b5-53 > 0.0 Hz
and the drive enables the integrator ramp limit, the PID integrator value limit is the range set by the output
frequency ±
b5-53
.
•
When the PID feedback changes quickly, gradually decrease the this parameter in 0.1 Hz increments to decrease the speed of the
response of PID control.
■
b5-54: PID Softstarter Selection
No.
(Hex.)
Name
Description
Default
(Range)
b5-54
(0BB7)
PID Softstarter Selection
Sets how the soft-starter responds to PID input/output.
0
(0, 1)
shows how the soft-starter responds to PID input/output.
Table 12.16 Soft Starter and PID Input/Output
Selection
PID Frequency Reference
Input
PID Frequency Reference
Output
Soft Starter Input
Soft Starter Output
Soft Starter 1
Frequency Reference
Soft Starter Input
PID Frequency Reference Output
Output Frequency
Soft Starter 2
Soft Starter Output
Output Frequency
Frequency Reference
PID Frequency Reference Input
0 : Disab PID Softstart
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...