494
SIEPCYEUOQ2V01A Q2V Technical Manual
■
C2-01: Jerk@Start of Accel
No.
(Hex.)
Name
Description
Default
(Range)
C2-01
(020B)
Jerk@Start of Accel
Sets the S-curve acceleration time at start.
Determined by A1-02
(0.00 - 10.00 s)
■
C2-02: Jerk@End of Accel
No.
(Hex.)
Name
Description
Default
(Range)
C2-02
(020C)
Jerk@End of Accel
Sets the S-curve acceleration time at completion.
0.20 s
(0.00 - 10.00 s)
■
C2-03: Jerk@Start of Decel
No.
(Hex.)
Name
Description
Default
(Range)
C2-03
(020D)
Jerk@Start of Decel
Sets the S-curve deceleration time at start.
0.20 s
(0.00 - 10.00 s)
■
C2-04: Jerk@End of Decel
No.
(Hex.)
Name
Description
Default
(Range)
C2-04
(020E)
Jerk@End of Decel
Sets the S-curve deceleration time at completion.
0.00 s
(0.00 - 10.00 s)
◆
C3: SLIP COMPENSATION
The Slip Compensation function improves the speed accuracy of an induction motor. As loads on induction
motors increase, motor slip increases and motor speed decreases. By adjusting the output frequency in accordance
with the motor load, it compensates the slip and makes the motor speed equal to the frequency reference.
■
C3-01: Slip Comp Gain
No.
(Hex.)
Name
Description
Default
(Range)
C3-01
(020F)
RUN
Slip Comp Gain
Sets the gain for the slip compensation function. Usually it is not necessary to change this setting.
Determined by A1-02
(0.0 - 2.5)
Note:
Correctly set these parameters before changing the slip compensation gain:
•
E2-01 [Mot Rated Current (FLA)]
•
E2-02 [Mot Rated Slip]
•
E2-03 [Mot No-Load Current]
Adjust this parameter as follows if necessary:
•
If the motor speed is slower than the frequency reference, increase this parameter in 0.1-unit increments.
•
If the motor speed is slower than the frequency reference value, decrease this parameter value in 0.1-unit
increments.
■
C3-02: Slip Comp Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
C3-02
(0210)
RUN
Slip Comp Delay Time
Sets the slip compensation delay time when speed is unstable or when the slip compensation
response is too slow. Usually it is not necessary to change this setting.
Determined by A1-02
(0 - 10000 ms)
Use these settings to adjust this parameter as necessary:
•
When the speed is not stable, increase the setting.
•
When the slip compensation response is too slow, decrease the setting.
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
V/f
OLV
OLV/PM
OLV/PM AOLV/PM
EZOLV
Summary of Contents for Q2V Series
Page 2: ...This Page Intentionally Blank 2 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 12: ...12 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 18: ...i 2 Legal Information 18 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 26: ...1 2 Features and Advantages of Control Methods 26 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 38: ...2 8 Installation Methods 38 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 70: ...3 3 Main Circuit Wiring 70 SIEPCYEUOQ2V01A Q2V Technical Manual Models B006 B012...
Page 102: ...3 17 Motor Application Precautions 102 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 138: ...4 12 Test Run Checklist 138 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 144: ...5 2 European Standards 144 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 145: ...Standards Compliance 5 5 2 European Standards SIEPCYEUOQ2V01A Q2V Technical Manual 145...
Page 146: ...5 2 European Standards 146 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 266: ...7 10 Troubleshooting Without Fault Display 266 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 284: ...8 6 Storage Guidelines 284 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 312: ...10 10 Peripheral Devices and Options 312 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 430: ...11 21 Parameters Changed by PM Motor Code Selection 430 SIEPCYEUOQ2V01A Q2V Technical Manual...
Page 731: ...SIEPCYEUOQ2V01A Q2V Technical Manual 731 Z Z pulse Auto Tuning 125...